Signet 5500 Flow Monitor

+

-

-

-

+

Relay 1 

Relay 2 

NC 

NO 

NC 

NO 

NC 

NO 

NC 

NO 

Device

A

External AC/DC

power

Device

B

5500

Terminals

Relay  

De-energized 

Relay  

Energized 

7. Relay 

Connections

Two internal relay contact sets (COM, NO, and NC) may be used 
for external device control. Front panel LED annunciators indicate 
the activation status of each relay. Each relay can control up to two 
devices simultaneously, as shown. Relay operation modes include 
Low alarm, High alarm, Pulse, and Totalizer (sec. 8.5).

Common device connections include:

•  Pulse mode - metering pump control
•  Pulse mode - solenoid valve control
•  Low or High mode - warning lamps
•  Low or High mode - bells or sirens
•  Low or High mode - external heavy-duty relay

Wiring Example Right

Device A IS powered when relay 2 is de-energized (front panel 
LED "off"). Power is discontinued when the relay 2 setpoint is 
reached (front panel LED "on"). Device B IS NOT powered when 
the relay 2 is de-energized. Power is applied after the relay 2 
setpoint is reached.

6.  4 to 20 mA Current Output Connections 

(sec. 8.4)

+

-

4-20

mA

5500 
Terminals

-

+

4

20

mA

*

Fuse**

1/8A

Technical Notes:

**  1/8 A fuse recommended (customer supplied)
*  4-20 mA output is internally powered (non-isolated), maximum 

loop impedance 350 

Ω

 with a 12 V instrument supply voltage, 

950 

Ω

 with a 24 V instrument supply voltage.

To isolate output and prevent ground loop problems:

1.  Use monitor device with isolated inputs, or
2.  Use separate DC supply for 5500 and monitor device, or
3.  Power 5500 with 12 - 24 VAC step-down transformer.

1 2

Total

reset

5500 
Terminals

Momentary pushbutton switch

5.  Totalizer Reset Connections 

(sec. 8.3)

Technical Notes:

•  Use 2-conductor shielded twisted pair cable for reset lines up to 

30 m (100 ft) max.

•  External reset switch overrides software security feature

(section 9.3 I).

•  To reduce the possibility of AC noise interference, isolate AC 

power lines from reset lines.

Technical Notes:

•  Maximum relay contact ratings:

5 A @ 30 VDC,
5 A @ 125 VAC, or
3 A @ 250 VAC

•  An external heavy-duty relay must be used for devices with surge 

or operating currents that exceed the above speci

fi

 cations.

Содержание Signet 5500

Страница 1: ...Double Insulated DC or AC power Contents 1 Power Connections 2 Compatible Sensor Wiring 3 Sensor Pulse Output Connections 4 Auxiliary Pulse Output Connections 5 Totalizer Reset Connections 6 4 20 mA...

Страница 2: ...t PNP source input 5500 Terminals External power supply 28 VDC max Other instrument Gnd Input NPN sink input Gnd AUX output N 5500 Terminals Signal output Signal ground 3 28 VDC External power supply...

Страница 3: ...wer is applied after the relay 2 setpoint is reached 6 4 to 20 mA Current Output Connections sec 8 4 4 20 mA 5500 Terminals 4 20 mA Fuse 1 8A Technical Notes 1 8 A fuse recommended customer supplied 4...

Страница 4: ...nsor also displayed on totalizer To enable the totalizer function the operator must set the relay or auxiliary pulse volume setpoint to 1 0000 sec 9 2 H 9 2 L Totalizer function ideal for external cou...

Страница 5: ...djustments ENTER OPTIONS sec 9 3 CALIBRATE sec 9 2 VIEW sec 9 1 2 seconds 5 seconds Press hold ENTER key for menu access Menu Displays A H Factory default displays shown A Flowrate and resettable tota...

Страница 6: ...disable hysteresis feature L Sets auxiliary output pulse volume setpoint 0 0001 99999 sec 8 2 Set to 1 0000 factory default to enable totalizer function sec 8 2 M Sets auxiliary output pulse width 0...

Страница 7: ...nds High 8 seconds also affects 4 to 20 mA output E Sets 4 mA output setpoint 4 mA and 20 mA setpoints are reversible F Sets 20 mA output setpoint 20 mA and 4 mA setpoints are reversible G Sets 4 mA c...

Страница 8: ...ilicone rubber Weight Approximately 500 g 18 oz Display Type Microprocessor controlled air core meter movement and backlit alphanumeric 2 x 16 LCD Update rate Flow 1s totalizer 200 ms Contrast User se...

Страница 9: ...96 mm 3 8 in RELAY 2 RELAY 1 ENTER 4 0 1 2 3 5 6 7 8 9 10 GPM Signet Monitor 92 x 92 mm 3 62 x 3 62 in Panel cutout Menu Parameters Display Description Range Factory Default A Flow rate and units Rese...

Страница 10: ...max _Gallons E Total K Factor 0 0001 99999 60 000 F Relay 1 mode Relay 1 setpoint Low or High 0 0000 99999 Pulse 0 0001 99999 Low 10 000 GPM G Relay 1 Hysteresis Hysteresis volume 0 0000 99999 2 0000...

Страница 11: ...l to D Display averaging Off 0 sec Low 4 sec High 8 sec Off E 4 mA setpoint Unlimited 0 0000 GPM F 20 mA setpoint Unlimited 100 00 GPM G 4 mA adjust 3 0 to 5 0 mA 4 00 mA H 20 mA adjust 19 to 21 mA 20...

Страница 12: ...mall Reduce auxiliary output pulse width setting sec 9 2 M or increase pulse volume setting sec 9 2 L Must be between 0 0001 99999 Relay 1 Relay 2 or Auxiliary output AUX pulse volume setpoint must be...

Отзывы: