TSA 160 NT and variants
32
Electrical installation and device settings
7.2.2 TSA 160 NT Invers limit stop
Factory setting: 0° door opening angle.
X
Hold the door in the closed position.
X
Set the blue cam plate (1) so that the limit switch
is operated in the closed position of the door.
X
Lightly tighten the countersunk screw (2) on the
end face.
7.2.3 Safety sensor (SIS, SIO)
The safety sensors (SIS, SIO) of all 1 to 2-leaf door systems have to be connected to the control of the drive belon-
ging to the door leaf.
When an SIS safety sensor is triggered, the closing door leaves reverse and open again.
When an SIO safety sensor is triggered the opening door leaf stops before the detected obstacle until the obstac-
le has been removed from the sensor’s field of detection. If the obstacle continues to be detected after a fixed
waiting period, the drive closes the door.
The yellow cam plate must be adjusted to hide structural areas (such as a wall) in the opening direction of the
respective door leaf .
Alternatively, wall blanking can also be realised by the safety sensor.
X
Open the door manually until the sensor (4)
signals the wall (5) by means of an indicator LED.
X
Move the door back until the LED goes out.
X
Jam the door with a wedge.
X
Lightly tighten the countersunk screw (2) at
the end face. Turn the yellow cam plate (3) in
the opening direction until the corresponding
micro-switch switches audibly.
X
Check the function by actuating the door.
X
Tighten the setscrews of the yellow cam plate.
4
5
2
3