Installation
3.2 Equipment and configuration of the MBZ300 control panel
Overview of the modules and components
à
Power module
PM
à
Power module extension
PME
à
Control module
CM
à
Sensor module
SM
à
Drive module
DM / DME
à
Weather module
WM
à
Relay module
ERM
à
Power pack 10 A, PS10A
à
Power pack 24 A, PS24A
Minimum and maximum equipment
à
The minimum equipment consists of 1 switching power supply unit, 1 power module
PM
, 1 control module
CM
and 1 drive module
DM
.
à
The maximum equipment can contain up to 64 BUS modules at a max. of 72 A (3 switching power supply units
with 24 A each). If more capacity is required, several units can be configured via the software as a combined unit.
3.2.1 Determining the correct equipment of the control panel
Switching power supply units and power modules
The number of switching power supply units and power module extensions
PME
required results from the
maximum drive current
. The power module
PM
is always required. One
PME
each is required for every further
switching power supply unit.
X
From the maximum current requirement you determine:
à
Number of switching power supply units (10 A or 24 A, max. 3 switching power supply units)
à
Number of power module extensions (
PME
, each 24 A max., 1 per switching power supply unit, max. 1
PM
+ 2
PME
)
à
Battery types for emergency power supply
Batteries for emergency power supply
X
Observe the following when selecting the batteries:
à
Back-up time for emergency power operation in case of power failure
à
Max. drive current
à
Number and types of the modules
à
Number of detectors connected
The emergency power supply has to be guaranteed for 72 h and motor operation then still has to be possible for
a subsequent 180 s (2x opening and 1x closing) at the maximum motor current.
Typical own consumption of the modules (with battery voltage 24 V)
à
Power module
PM
16.1 mA
à
Power module extension
PME
0.0 mA
à
Control module
CM
20.6 mA (incl. 3 detector line caps)
à
Sensor module
SM
12.6 mA (incl. 3 detector line caps)
à
Drive module
DM
5.3 mA
à
Drive module
DME
5.3 mA
à
Weather module
WM
13.0 mA
à
CAN
module
6.0 mA
à
Relay module
ERM
6.0 mA
Maximum permissible own current consumption for all control panel modules
SNT / Battery
7 Ah
12 Ah
17 Ah
24 Ah
38 Ah
8 A
48 mA
10 A
42 mA
120 mA
140 mA
240 mA
350 mA
24 A
70 mA
120 mA
200 mA
300 mA
48 A
80 mA
170 mA
300 mA
72 A
100 mA
300 mA
SNT = switching power supply unit
Consider the control cabinet size when selecting the batteries.