MBZ300
4
Safety instructions
Duties of the owner-operator
X
Secure workplace against unauthorised entry.
X
Ensure that mounting, commissioning and maintenance are only carried out by qualified personnel author-
ised by GEZE. If unauthorised changes are made to the system, GEZE cannot be made liable in any way what-
soever for any resulting damages.
X
Ensure that the keys for the control cabinet and the RWA button are only available to instructed personnel.
Electrical system
X
Before working on the electrical system, disconnect the power supply (mains and battery) and verify the safe
isolation from supply.
X
Ensure that only a trained electrician completes the connection to the mains voltage. The power connection
and safety earth conductor test must be carried out in accordance DIN VDE 0100-600.
X
Make sure that work is always only done by a qualified electrician or a “qualified electrician for restricted work”.
X
An on-site, 2-pole circuit breaker with locking option is to be used as a line-side disconnecting device, in
accordance with the permissible cable current load.
Live parts are exposed after the system housing has been opened. The system must be disconnected from the
supply and battery voltage before every intervention in the control panel. The supply terminals of the system
components partially have a low voltage of ≤50 V.
X
Do not the activate the mains and battery voltage until all system components have been connected.
X
When replacing the batteries use only batteries approved by GEZE.
X
Ensure that the control panel cannot be opened by unauthorised persons.
X
Use only the cables specified on the cable plan provided. Cables must be shielded in compliance with the
wiring diagram.
X
Determine cable types (e.g. fire control cable) and required IP rating in agreement with the local official ap-
proval authority.
X
As a rule, always use insulated wire cores.
X
Insulate wires that are not used.
X
Secure loose cables with cable ties.
Maintenance
A safety-related test with maintenance has to be carried out by a GEZE-authorised specialist as required – at least
once a year. You will receive written verification about the check. All batteries must be replaced every four years
at the latest.
Spare parts
GEZE does not accept any warranty for combinations with third-party products.
X
Use only original GEZE parts for repair and maintenance work.
Regulations and standards
Warranty claims require assembly, installation and service to be performed by a specialist company according
to the manufacturer's specifications. The owner-operator and/or installer commissioned by the owner-operator
must observe all relevant legal regulations and have been briefed on proper operation.
X
Perform system maintenance according to legal regulations.
X
Observe the maintenance specifications.
X
Observe the latest versions of directives, standards and country-specific regulations, in particular:
à
ASR A1.6 “Windows, fanlights, translucent walls”
à
DIN VDE 0100-600 “Setting up low-voltage systems”
à
DIN EN 60335-2-103 “Household and similar electrical appliances - Safety; Particular requirements for drives
for gates, doors and windows”
à
Accident prevention regulations, especially DGUV regulation 1 “Accident prevention regulation, basics of
prevention” and DGUV regulation 3 “Accident prevention regulation, electrical installations and equipment”
à
VDE 0833 “Danger alarm systems for fire, break-in and assault”
à
VDE 0815 “Installation cable and lines for remote and information processing systems”
à
MLAR “Model Guideline for Line Systems”