MBZ300
13
Installation
3.3 Connection of the MBZ300 control panel
The following three connection types exist for the modules:
à
Supply voltage
à
Power module
PM
à
Power module extension
PME
à
Drive module
DM
à
BUS connection (ribbon cable)
à
All the modules (only connection
PME
–
PM
on the module top, remaining modules on the bottom)
à
External components
à
Detectors, drives etc. (plug-in terminals on the module top)
3.3.1 Connection of the supply voltage
The following must be connected (if not already done in the factory):
à
Internal power supply
à
Batteries (also have to be placed in the central housing)
à
Switching power supply units to the power module
PM
and, if necessary, power module extensions
PME
à
Drive modules
DM
to the supply voltage
All the other modules do not require a connection to the supply voltage. The following diagrams show the con-
nection for:
à
1
power module
PM
with
1
switching power supply unit 10 A or 24 A (with MBZ300 N8 max. 8 A)
à
1
power module
PM
with
1
power module extension
PME
and
2
switching power supply units 10 A or 24 A
à
1
power module
PM
with
2
power module extensions
PME
and
3
switching power supply units 10 A or 24 A
The number of drive modules
DM
that can be connected to a switching power supply unit with
PM
or
PME
de-
pends on the maximum current consumption at the respective switching power supply unit.
Application examples:
à
Switching power supply unit 10 A with
1
DM
for max. 10 A current consumption (for MBZ300 N8 max. 8 A)
– or –
Switching power supply unit 10 A with
2
DM
for two ventilator groups with max. 5 A current consumption each
à
Switching power supply unit 24 A for
2 DM
with max. 10 A current consumption each
– or –
Switching power supply unit 24 A for
4
DM
, if the max. current consumption does not exceed 10 A per
DM
and 24 A in total
Connection with one switching power supply unit
N L
Rdy
+ + - -
DC ON
DC LO
parallel
single
Rdy
+ +
- -
Switching power supply unit
Operating display (green)
Status display (green)
Fault display (yellow)
25A
Safety fuse
Bus to
CM
–P
ower supply
–D
rive module DM
–B
atteries
blue
red
3 1
2 1
+P
ower supply
+D
rive module DM
+B
atteries
fron
t
Battery 1
12 V
Battery 2
12 V
+
+
-
-
Note polarity !
blue
red
blue
red
Power module
PM
Operating display (green)
Fault display (yellow)
Alarm (EMERGENCY OPEN) display (red)
Bus
Module output
Bus
52 51 1
Display OPEN drives (red)
Display CLOSE drives (green)
open
close
Push button drives
10A
Safety fuse
3 2 1
–2
4V
+2
4V
to the
next
DM
33 32 1
35
36
37
–2
4V
+2
4V
Drive module
DM
Module input
blue
red
blue
red
fron
t
Note the sequence
of the connections
max. 10 / 24 A
Note max.
permissible
power consumption !
red
blue
230 V
with 10 A
red
blue
/ 24 A
with 24 A
L
N
230 V AC
PE
230 V
0
1 A