24
Basic Settings
– continued –
To prevent oscillation or repeated activationdeactivation cycles of the controlled system, a deadband
can be defined for the septpoint “W”.
The setpoint is defined by the proportional range which is limited by the switchpoints 2 and 3. To set
the code switch
8
remove the terminal strip
9
.
Dead band
Code switch settings
Fig. 16
S 1
S2
S3
S4
S5
S6
S7
S8
S9
S10 Deadband
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
0 %
OFF OFF OFF OFF OFF OFF OFF
ON
OFF OFF
1 %
OFF OFF OFF OFF OFF OFF OFF OFF
ON
OFF
2 %
OFF OFF OFF OFF OFF OFF OFF
ON
ON
OFF
3 %
OFF OFF OFF OFF OFF OFF OFF OFF OFF
ON
5 %
OFF OFF OFF OFF OFF OFF OFF
ON
OFF
ON
7 %
OFF OFF OFF OFF OFF OFF OFF OFF
ON
ON
10 %
OFF OFF OFF OFF OFF OFF OFF
ON
ON
ON
15 %
8
Establishing / changing the dead band
Write down the node ID and baud rate settings.
Node ID in this example: 40
Baud rate in this example: 250 kBit/s
Switch off mains voltage.
The four status LEDs go out.
The LED “Power” goes out.
Содержание NRR 2-40
Страница 1: ...1 E N English Level Controller NRR 2 40 Original Installation Instructions 810369 06 ...
Страница 9: ...9 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Страница 10: ...10 Design 0 Fig 3 9 NRR 2 40 9 a ...
Страница 11: ...11 Functional Elements NRR 2 40 Fig 5 Fig 4 1 7 6 5 4 3 2 8 ...
Страница 13: ...13 Installation continued Fig 6 Example of Installation b 9 0 0 Fig 7 20 20 a ...
Страница 17: ...17 Fig 10 NRR 2 40 as continuous controller Wiring diagram Electrical Connection continued d e g l h k i l ...