23
Fig. 13 (Factory setting)
Fig. 14 (Example 1)
Fig. 15 (Factory setting 250 kBit/s)
Basic Settings
– continued –
Code switch settings
8
8
Node ID
40
S 1 OFF
1
S 2 OFF
2
S 3 OFF
4
S 4
ON
8
S 5 OFF
16
S 6
ON
32
S 7 OFF
64
Node ID
75
S 1
ON
1
S 2
ON
2
S 3 OFF
4
S 4
ON
8
S 5 OFF
16
S 6 OFF
32
S 7
ON
64
S 8 S 9 S 0
Baud rate
Cable length
OFF
ON
OFF
250 kBit/s
125 m
ON
ON
OFF
125 kBit/s
250 m
OFF
ON
ON
100 kBit/s
335 m
ON
ON
ON
50 kBit/s
500 m
OFF
ON
ON
20 kBit/s
1000 m
ON
ON
ON
10 kBit/s
1000 m
Establishing / changing node ID
If several identical systems are to communicate in a CAN bus network, allocate a different node ID for
each system (e. g. limiter, controller, etc). In most cases it is sufficient to commission the equipment
with the default factory settings.
To set the code switch
8
remove the lower terminal strip
9
.
Attention
n
We recommend that you commission the CAN bus devices with the default factory
setting.
n
Do
not
use a node ID for more than one piece of equipment in the CAN bus system.
Содержание NRR 2-40
Страница 1: ...1 E N English Level Controller NRR 2 40 Original Installation Instructions 810369 06 ...
Страница 9: ...9 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Страница 10: ...10 Design 0 Fig 3 9 NRR 2 40 9 a ...
Страница 11: ...11 Functional Elements NRR 2 40 Fig 5 Fig 4 1 7 6 5 4 3 2 8 ...
Страница 13: ...13 Installation continued Fig 6 Example of Installation b 9 0 0 Fig 7 20 20 a ...
Страница 17: ...17 Fig 10 NRR 2 40 as continuous controller Wiring diagram Electrical Connection continued d e g l h k i l ...