19
Electrical Connection
– continued –
CAN bus wiring diagram
Fig. 11
RES 2
CEP
NRS, NRR, LRR,
TRS, URB 1
URB 2
NRG, LRG,
EF, URZ
TRV
RES 1
Attention
n
Wire equipment in series. Startype wiring is not permitted!
n
Link screens of control cables such that electrical continuity is ensured and connect
them
once
to the central earthing point (CEP). If equipotential bonding currents are
to be expected, for instance in outdoor installations, make sure that the screen is
separated from the central earthing point (CEP).
n
To protect the switching contacts fuse circuit with T 2.5 A or according to TRD
regulations (1.0 A for 72 h operation).
n
If two or more system components are connected in a CAN bus system, provide the
first and the last device with a terminating resistor of 120
Ω
,
Fig. 11
n
Do
not
interrupt the CAN bus network during operation with one or more system
components!
If the CAN bus network is interrupted the safety circuit will be opened.
If the control unit has to be replaced, detach terminal strips
9
.
Fig. 3
Before taking the CAN bus line from the terminal strip, make sure that all connected
system components are out of service.
Содержание NRR 2-40
Страница 1: ...1 E N English Level Controller NRR 2 40 Original Installation Instructions 810369 06 ...
Страница 9: ...9 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Страница 10: ...10 Design 0 Fig 3 9 NRR 2 40 9 a ...
Страница 11: ...11 Functional Elements NRR 2 40 Fig 5 Fig 4 1 7 6 5 4 3 2 8 ...
Страница 13: ...13 Installation continued Fig 6 Example of Installation b 9 0 0 Fig 7 20 20 a ...
Страница 17: ...17 Fig 10 NRR 2 40 as continuous controller Wiring diagram Electrical Connection continued d e g l h k i l ...