14
Closing temperature
[°C]
Set value [mm]
DN15 DN20,
DN25
DN40
20
22.4
23.6
41.8
25
22.8
24.2
42.7
30
23.2
24.8
43.6
35
23.6
25.3
44.4
40
24.0
25.8
45.2
45
24.4
26.4
46.0
50
24.8
26.9
46.8
55
25.2
27.4
47.6
60
25.6
28.0
48.5
65
26.0
28.5
49.3
70
26.4
29.0
50.1
75
26.7
29.5
50.9
80
27.1
30.1
51.7
85
27.5
30.7
52.4
90
27.9
31.3
53.0
95
28.3
31.8
53.5
100
28.7
32.3
54.0
105
29.0
32.8
54.4
110
29.4
33.3
54.8
115
29.8
33.8
55.1
120
30.2
32.7
55.5
125
30.6
33.0
55.8
130
30.9
33.3
56.2
135
31.2
33.6
54.5
140
31.5
34.0
54.8
145
30.4
34.3
55.0
150
30.7
34.6
55.3
155
31.0
34.9
55.5
160
31.2
35.1
55.7
The set value is based on ambient temperatures of
18 – 21 °C. If the ambient temperature is higher or
lower use the following table to adjust the set value.
Ambient temperature
[°C]
Correction value [mm]
DN15 DN20,
DN25
DN40
9–12
+0.75 +0.9 +1.5
12–15
+0.5 +0.6 +1.0
15–18
+0.25 +0.3 +0.5
18–21
0
21–24
–0.25 –0,3 –0.5
24–27
–0.5 –0.6 –1.0
27–30
–0.75 –0.9 –1.5
Please contact the manufacturer if the
ambient temperature passes outside the
indicated temperature range.