Troubleshooting
Fault
Cause
Remedy
Equipment does not control
correctly.
The Thermovit regulator is
contaminated.
Remove Thermovit regulator.
Rinse equipment.
Rinse Thermovit regulator.
Mount Thermovit regulator.
The Thermovit regulator is
damaged.
Discard and replace Thermovit regulator.
The outlet temperature exceeds
the adjusted closing
temperature.
The leak passage is too high.
The design data for sizing the
equipment was wrong.
Change the settings of the installation or
mount correctly sized equipment.
The intended flowrate or the
service temperature are not
reached.
The design data for sizing the
equipment was wrong.
The settings of the installation
differ from the design data.
If faults occur that are not listed above or cannot
be corrected, please contact our Technical
Service or authorized agency in your country.