Mounting Thermovit regulator after purging
Remove the cover as described on page 18.
Attention!
Malfunctions due to inadvertent
misadjustment of Thermovit regulator.
Make sure that the setting of the
Thermovit regulator is not changed
when mounting or servicing the
equipment.
Fasten the Thermovit regulator with the
following tightening torque:
DN15 to DN25: 90 Nm
DN40: 140 Nm.
Attach cover to the equipment as described on
page 18.
Maintaining equipment
The equipment is maintenance-free.
Servicing equipment
You may exchange the following component parts
in case of wear or damage:
Thermovit regulator
Gasket between cover and body
External setting device (if provided)
Gasket for external setting device (if provided)