3. COMMAND LIST
3.1 BRnnn
This command is not displayed in the help text (?<ENTER>). Displays or sets the current baud
rate. Valid numbers for “nnn” are 9 (9600 baud) or 115 (115,200 baud). The example below
changes the baud rate to 9600 with no confirmation.
*BR9
3.2 C
Display the current datalogger real-time clock settings. The
CS
command section explains how
to adjust the clock settings.
*C
Date: 02/21/07 Time: 10:43:08
*
3.3 CSmm/dd/yy/hh:mm:ss
Set the datalogger’s internal real time clock; mm represents the month, dd the day of the month,
yy the year, hh the hours, mm the minutes, and ss the seconds. Illegal combinations will be
ignored (i.e. CS02/30/07 or CS///12:60). Fields can be left blank to avoid changing (i.e. CS//07 to
just change the year).
*CS///10:45:00
Date: 02/21/07 Time: 10:45:00
*
Note: If logging is currently started and the clock is changed, a restart of the scan interval or log
interval table will occur.
3.4 DEFAULT
The DEFAULT command will reload the datalogger’s channel and gage settings to the factory
default settings. This results in:
All channels Enabled
All Gage Types set to 1
All Zero Readings set to 0.00000
All Gage Factors set to 1.00000
All Gage Offsets set to 0.00000
Scan interval = 30S
Log Interval Table default values (Sections 3.13 and 3.14)
All readings synchronized to the top of the hour
Memory will wrap when full and continue logging
All Thermistors set to standard temperature