830209G/160228
-
Tekniske ændringer forbeholdes
- Technische Änderungen vorbehalten - Subject to Technical Modifications -
41
Optima 300
it may be necessary to change this temperature. The
temperature may be set between 0 - 10°C
.
51: Temp dif.
As standard the temperature difference between start-
stop compressor is ±0,4°. Under special conditions,
it will be an advantage to change the temperature
difference. The difference may be set between 0,1-1,0°.
5: R9 function
This relay may be used as follows:
If the setting is 0, the relay is off.
If the setting is 1, the relay is on when the unit runs.
If the set point is 2, the relay is on when additional
heating is needed
If the set point is 3, the relay is on when the filters need to
be changed.
If the set point is 4, the relay is on when extra cooling is
required.
If the set point is 5, the relay is on when air can be taken
through a Ground Collector in advantage.
ENGLISH