Optima 300

38: Default values
Please notice: before resetting the values please 
ensure that the actual set points are noted in the 
scheme page 43.
 

Here is an option for re-adjusting the set points to default, 

in case the unit will not meet the requirements and 

the cause is impossible to locate. Note all set points in 

the schedule. Adjust the set point to 1 and press OK. 

Hereafter all set points will be adjusted to factory default, 

except the fan speeds and contrast settings.
To reset all to factory settings adjust the set point to 2 and 

press OK. It is now possible to start all over and adjust 

the set points. Remember to adjust fan speeds at Level 1, 

2 and 3 as previous, as these are the numbers to which 

the unit was initially adjusted.

39: Preheat ON

If a pre-heating surface has been mounted on the fresh 
air duct, the set point must be adjusted to 1. If, instead, 
an extra cooling surface has been mounted on the supply 
air duct, the set point must be adjusted to 0. (It is not 
possible to control both pre-heating surface and extra 
cooling unit). If both setting of 20 seconds. The regulator 

time may be adjusted between 1 – 250 extra items have 

been mounted, the set point must be changed manually 

every spring and autumn or use relay 9, menu point 52, 

for controlling the extra cooling.

40: Preheat temp

If pre-heating ON is connected, the set point must be 

adjusted to the desired fresh air temperature to which the 

pre-heating surface must heat the fresh air upstream of 

the unit. The temperature may be set between -15 - 0°C.

>> Antifreeze ON

42 Antifreeze set

43 T2 adjustment

44 Program info

Set point

Operations menu

Exit

OK

<

>

0

41: Antifreeze ON

If a water re-heating surface with motor valve has been 

mounted on the unit, a freezing water sensor can be 

mounted on the water reheating surface. Adjust the set 

point to 1. If no freezing water sensor has been mounted, 

the set point must be set to 0.

4: Antifreeze set

If freezing water has been switched to ON, the set point 

must be adjusted to the desired temperature at which the 

freezing water sensor is to stop the unit. The temperature 

may be set between 0 - 10°C.

43: T adjustment

It is possible to adjust the room sensor on the control 

panel so that the display shows the correct room 

temperature. The temperature may be set between -5 

- 0°C.

44: Program info

The set point is always 0. If you press OK; the display will 

show the installed program version for the heat pump. At 

the same time, an automatic exit will be made from the 

operating menu. 

>> Water reg sec

46 Heating reg min

47 Preheat extra

48 Preheat temp

Set point

Operations menu

Exit

OK

<

>

0

45: Water reg sec

If a water after-heating coil has been installed in the 

supply air duct, it may be necessary to change the 

regulator time, which has a standard setting of 20 

seconds. The regulator time may be adjusted between 1 

– 250 seconds.

46: Heating reg min

If the electric pre-heating or electric post-heating surface 
has been mounted, it may be necessary to change the 

regulator time, which has a standard setting of 3 minutes. 

The regulator time can be adjusted between 1 -30 

minutes.

47: Preheat extra

If a pre-heating surface has been mounted on the fresh 

air duct with an extra relay circuit board, the set point 

must be adjusted to 1. If no extra relay circuit board has 
been mounted, the set point must be adjusted to 0.

48: Preheat temp

If an electric pre-heating surface has been mounted, the 

desired temperature of the fresh air drawn in through the 

unit may be set. The temperature may be set between 

-15 - 0°C.

>> Bedroom

50 Stop defrosting

51 Temp dif

52 R9 function

Set point

Operations menu

Exit

OK

<

>

0

49: Bedroom

If you wish to control the temperature in the bedroom 

and do not want to supply with to hot air, you have the 

possiblility to mount an extra damper between the supply 

boss and the bedroom boss. If so please set menu 52 

point 6 on ON.

Set point can be set between 10°-25°C

50: Stop defrosting

As standard, the defrosting period will stop when the 

cooling surface has reached a temperature of 5°C, which 

is the standard setting. In particular operating stages, 

ENGLISH

Содержание Optima 300

Страница 1: ...betjeningsvejledning Gebrauchsanweisung User Manual Optima 300 Varmepumpe W rmepumpe Heat pump Version 3 02 0107...

Страница 2: ...1 3 Betriebsmen 20 1 4 Wochenprogramm 25 1 5 Abtauschema 25 1 6 Spezielle Funktionen 26 1 7 Schema f r Sollwerte 27 2 Funktion 2 1 Steuerung Optima 300 28 2 2 Zus tzliche Funktionen 28 2 3 Betriebssic...

Страница 3: ...1 Supply T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling T6 Coil cooling T7 Extract air T8 Antifreeze T9 Solar collector R1 Compressor R3 Pre heat R2 Supp heat R8 Cooling R5 Heat level 2 R1...

Страница 4: ...Min cooling ON To prevent the unit from starting to cool during the winter regardless of how high the room temperature is the set point may be adjusted to the desired minimum outdoor temperature befo...

Страница 5: ...g with the actual unit If the air volumes are set lower than the minimum requirement the heat pump will stop and only pre heated air will be blown from the heat exchanger into all rooms Units without...

Страница 6: ...the week Monday 1 Tuesday 2 Wednesday 3 Thursday 4 Friday 5 Saturday 6 Sunday 7 Clock hour 30 Clock minute 31 Change day 32 Change point Set point Operations menu Exit OK 0 29 Clock hour Adjust the se...

Страница 7: ...ust be set to 0 42 Antifreeze set If freezing water has been switched to ON the set point must be adjusted to the desired temperature at which the freezing water sensor is to stop the unit The tempera...

Страница 8: ...tage to change the temperature difference The difference may be set between 0 1 1 0 52 R9 function This relay may be used as follows If the setting is 0 the relay is off If the setting is 1 the relay...

Страница 9: ...urs Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Wednesday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1...

Страница 10: ...ontrast of the display can be changed by pressing the Info button while the program info screen is displayed Use the arrows to adjust up or down You can also enter menu 44 press OK and then hold the i...

Страница 11: ...20 Room supply extract 0 0 0 0 c 5 0 C 21 Airflow 1 SUP 40 0 100 22 Airflow 2 SUP 70 0 100 23 Airflow 3 SUP 100 0 100 24 Airflow 1 EXT 35 0 100 25 Airflow 2 EXT 55 0 100 26 Airflow 3 EXT 70 0 100 27 C...

Страница 12: ...will perform control in the same way as the electric re heating surface Defrosting When the temperature difference between the temperature upstream of the cooling surface and the temperature of the c...

Страница 13: ...frame and washed in warm soapy water Keep the filter diagonally so the water runs out The filter must not be wrung out or washed in dishwasher After two or three washes replace the flat filter Place...

Страница 14: ...here power in the electric outlet Is the heat pump disconnected through the clock program Has the high pressure switch been activated The cable between the controller and the panel is mounted Has the...

Страница 15: ...oller panel 0V 10V TX RX Motor Valve 24 VDC 0V 0 10V El heater 1 2 Kw Step1 Relay 2 Extra Cooling Upstream Coil 0 8 KW Relay 3 Magnetic valve Defrosting Relay 4 Relay outlet For extra print For El hea...

Страница 16: ...t Air Heat exchanger Supply Air T4 T5 T3 T6 T1 MA4 Compressor T7 Control panel High pressure switch T2 Fresh Air Evaporator cooling coil High pressure switch Condenser heating coil Heat exchanger MA4...

Страница 17: ...ject to Technical Modifications 830209G 160228 Optima 300 8 Flow diagram GE Mini Midi C High pressure switch MA4 Compressor Controller panel MA7 HP Supply air Exhaust air T2 T3 Fresh air Evaporator co...

Страница 18: ...8307 Effretikon Tel 41 0 52 355 11 00 Fax 41 0 52 355 11 05 E Mail info sm heag ch 6 Tyskland Deutschland Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E M...

Отзывы: