background image

830209G/160228 

 

Tekniske ændringer forbeholdes 

- Technische Änderungen vorbehalten - Subject to Technical Modifications -

 

39 

Optima 300

23: Airflow 3 SUP

Level 3 is the highest speed and is in use when having 

many guests, when airing the room, having major activity 

in the kitchen, or if the unit is used for ventilating offices, 

institutions etc. The provisional factory setting is 100%. 

Remember that all over-ventilation is a waste of energy.

24: Airflow 1 EXH

Remember if the air volume is set lower than the 

minimum air volume in point 16, the heat pump will switch 

off.
The provisional factory setting is 35%.

>> Airflow 2 EXH

26 Airflow 3 EXH

27 Clock ON

28 Clock day

Set point

Operations menu

Exit

OK

<

>

0

25: Airflow 2 EXH

The provisional factory setting is 55%.

26: Airflow 3 EXH

The provisional factory setting is 70%.

7: Clock ON
Please Notice: The adjustment of the weekly clock 

can easily be adjusted after manually filling out the 

weekly program scheme at page 42. 

If it is wished to control the unit with the weekly clock, the 

set point must be adjusted to 1. The weekly clock allows 

the speed to be changed automatically up to 10 times 

per day, while at the same time the room temperature 

may be changed to a lower temperature for each change 

period than the set temperature in point 2. If the speed 

or room temperature is changed with the short-cut keys 

on the main menu, the weekly program will automatically 

cut in again, when passing the time of change. If it is 

desired only to change the speed and room temperature 
manually, the set point should be adjusted to 0.

8: Clock day

Starting the clock. Adjust the set point to the relevant day 

of the week.

Monday = 1, Tuesday = 2, Wednesday = 3, Thursday = 4, 

Friday = 5, Saturday = 6, Sunday = 7

>> Clock hour

30 Clock minute

31 Change day

32 Change point

Set point

Operations menu

Exit

OK

<

>

0

9: Clock hour

Adjust the set point to the relevant number of hours.

30: Clock minute

Adjust the set point to the relevant number of minutes.

31-36:

When the marker “>>” is pointing to menus between 

31 and 36 the display heading changes to show actual 

changing point according to the following format: 

Changepoint, Weekday, Time. Example: “3 Monday 

20:36”

Before compiling a personal weekly program it may be a 

fine help filling out the week schedule included.

31: Change day

Adjust the set point at the actual day of the week, in 

which you wish to adjust the changeover times. 

Monday = 1, Tuesday = 2, Wednesday = 3, Thursday = 4, 

Friday = 5, Saturday = 6, Sunday = 7

3: Change point

Adjust the set point to the desired changeover time. May 
be set up to ten times each day.

>> Change hour

34 Change minutes

35 Change airflow

36 Change room temp

Set point

Operations menu

Exit

OK

<

>

0

33: Change hour

Adjust the set point to the hour at which a changeover is 

desired.

34: Change minutes

Set the set point to the minute at which it is desired to 

perform the changeover.

35: Change Airflow

Set the set point to the step (speed) at which it is desired 

to perform the changeover. 

36: Change room temperature

Adjust the wanted set point to the number of degrees 

lower, compared to the set room temperature in point 2 

for this changing period.

>> Copy day

38 Default values

39 Preheat ON

40 Preheat temp

Set point

Operations menu

Exit

OK

<

>

0

37: Copy day

It is possible to adjust the set point to copy the weekly 

program of the actual day to the one chosen by the 

setting. E.g. if menu point 18 is adjusted to set point 2 

(Tuesday), the weekly program for Tuesday will be copied 

to the day chosen by this setting.

ENGLISH

Содержание Optima 300

Страница 1: ...betjeningsvejledning Gebrauchsanweisung User Manual Optima 300 Varmepumpe W rmepumpe Heat pump Version 3 02 0107...

Страница 2: ...1 3 Betriebsmen 20 1 4 Wochenprogramm 25 1 5 Abtauschema 25 1 6 Spezielle Funktionen 26 1 7 Schema f r Sollwerte 27 2 Funktion 2 1 Steuerung Optima 300 28 2 2 Zus tzliche Funktionen 28 2 3 Betriebssic...

Страница 3: ...1 Supply T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling T6 Coil cooling T7 Extract air T8 Antifreeze T9 Solar collector R1 Compressor R3 Pre heat R2 Supp heat R8 Cooling R5 Heat level 2 R1...

Страница 4: ...Min cooling ON To prevent the unit from starting to cool during the winter regardless of how high the room temperature is the set point may be adjusted to the desired minimum outdoor temperature befo...

Страница 5: ...g with the actual unit If the air volumes are set lower than the minimum requirement the heat pump will stop and only pre heated air will be blown from the heat exchanger into all rooms Units without...

Страница 6: ...the week Monday 1 Tuesday 2 Wednesday 3 Thursday 4 Friday 5 Saturday 6 Sunday 7 Clock hour 30 Clock minute 31 Change day 32 Change point Set point Operations menu Exit OK 0 29 Clock hour Adjust the se...

Страница 7: ...ust be set to 0 42 Antifreeze set If freezing water has been switched to ON the set point must be adjusted to the desired temperature at which the freezing water sensor is to stop the unit The tempera...

Страница 8: ...tage to change the temperature difference The difference may be set between 0 1 1 0 52 R9 function This relay may be used as follows If the setting is 0 the relay is off If the setting is 1 the relay...

Страница 9: ...urs Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Wednesday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1...

Страница 10: ...ontrast of the display can be changed by pressing the Info button while the program info screen is displayed Use the arrows to adjust up or down You can also enter menu 44 press OK and then hold the i...

Страница 11: ...20 Room supply extract 0 0 0 0 c 5 0 C 21 Airflow 1 SUP 40 0 100 22 Airflow 2 SUP 70 0 100 23 Airflow 3 SUP 100 0 100 24 Airflow 1 EXT 35 0 100 25 Airflow 2 EXT 55 0 100 26 Airflow 3 EXT 70 0 100 27 C...

Страница 12: ...will perform control in the same way as the electric re heating surface Defrosting When the temperature difference between the temperature upstream of the cooling surface and the temperature of the c...

Страница 13: ...frame and washed in warm soapy water Keep the filter diagonally so the water runs out The filter must not be wrung out or washed in dishwasher After two or three washes replace the flat filter Place...

Страница 14: ...here power in the electric outlet Is the heat pump disconnected through the clock program Has the high pressure switch been activated The cable between the controller and the panel is mounted Has the...

Страница 15: ...oller panel 0V 10V TX RX Motor Valve 24 VDC 0V 0 10V El heater 1 2 Kw Step1 Relay 2 Extra Cooling Upstream Coil 0 8 KW Relay 3 Magnetic valve Defrosting Relay 4 Relay outlet For extra print For El hea...

Страница 16: ...t Air Heat exchanger Supply Air T4 T5 T3 T6 T1 MA4 Compressor T7 Control panel High pressure switch T2 Fresh Air Evaporator cooling coil High pressure switch Condenser heating coil Heat exchanger MA4...

Страница 17: ...ject to Technical Modifications 830209G 160228 Optima 300 8 Flow diagram GE Mini Midi C High pressure switch MA4 Compressor Controller panel MA7 HP Supply air Exhaust air T2 T3 Fresh air Evaporator co...

Страница 18: ...8307 Effretikon Tel 41 0 52 355 11 00 Fax 41 0 52 355 11 05 E Mail info sm heag ch 6 Tyskland Deutschland Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E M...

Отзывы: