Optima 300

1: Reduce sup. Air

If set point 1 has been selected under point 11, it is 
recommended that the external temperature is set to -

10°C.The set point may be set between 0 - -15°C.

>> Airflow suppl.

14 Filter change

15 Hold ON-OFF

16 Min. airflow

Set point

Operations menu

Exit

OK

<

>

0

13: Airflow suppl.

If set point 1 is selected in menu 11 it is recommended 

that the supply air volume is adjusted to 20% lower 

 

than the set value in menu point 22.

14: Filter change

The control system contains an integral timer which 

counts the time for which the unit has been in operation 

since the last filter change. It is recommended that the 

set point is initially set to 3, meaning three months. If the 

filters are too dirty, the set point may be reduced. If it is 

unnecessary to change the filters after three months, 

the set point may be increased. The set point may be 

adjusted between 1-6, equal to 1-6 months. When the 

timer reaches the set value for filter change, the red 

Genvex logo will begin to flash on the control panel and 

the words “change filter” will appear on the display. The 

Genvex logo will continue to flash until the filters are 

changed. When the filters are changed the filter timer 

can be reset by pressing ”enter ” in 10-15 sec. until the 

Genvex logo begins to flash again and the equipment is 

back in normal operation.

15: Hold ON-OFF

To avoid forgetting the change of filters allthough 

the Genvex logo is flashing on the control panel, the 

set point may be adjusted to 1. In this case, the unit 

will automatically stop after 14 days, if the filters 

have not been changed in the meantime. If this safety 
feature is not desired, the set point may be adjusted to 

0, and the Genvex logo will keep on flashing until the 

filters are changed.

16: Min. airflow

To achieve optimum operation of the unit, the unit air 
volume must, as a minimum, conform to the values  

described in the brochure dealing with the actual unit. 

If the air volumes are set lower than the minimum 

requirement, the heat pump will stop and only pre-heated 

air will be blown from the heat exchanger into all rooms. 

Units without heat exchanger will blow external air 

directly into the rooms. The minimum air volume is set by 
the initial adjustment of the unit. The provisional factory 

setting, is meanwhile 40%.

>> Extended airflow

18 Hour

19 Not in use

20 Room/supply/extract

Set point

Operations menu

Exit

OK

<

>

0

17: Extended airflow

At 3rd speed, there is an option of making the unit step 

down automatically to the 2nd speed, after a number of 

hours, by adjusting to set 1. If the set point is adjusted 

to 0, the unit will run at the 3rd speed until a lower 

speed has been selected manually.

18: Hour

If automatic stepdown at 3rd speed, is in use, the number 

of hours at which the unit is to operate with forced 

air, may be adjusted here. The set point may be adjusted 

between 1 – 10 hours.

19: Not in use

Set point must be 0

0: Room/supply/extract

There is a choice between room control, supply air or 

extract control. If the unit is installed in the home, 
the unit must be set to room control by adjusting the set 
point to 0.0. If the set point is adjusted to 0,1, the 

unit will switch to supply control. At 0,2 the extract 

control is activated. 

>> Airflow 1 SUP

22 Airflow 2 SUP

23 Airflow 3 SUP

24 Airflow 1 EXT

Set point

Operations menu

Exit

OK

<

>

0

21: Airflow 1 SUP

Level 1 is the lowest speed which may be used when 

being out of the home, e.g. on holidays or weekends. 

Both fans may be set independently at all levels, to 
achieve the same air volume on the supply side as on 
the extract side, thus giving optimum operation. Initial 

adjustment of the unit must be performed with technical 

air measurement equipment, and may be done without 

 

using the main adjustment damper. Remember if the air 

volume is set lower than the minimum air volume in point 

16, the heat pump will switch off. The provisional factory 

setting is 40%.

22: Airflow 2 SUP

Level 2 is the normal operating speed for the unit, 
providing the optimum internal climate and must be 
regulated to the ventilation needs of the individual 
home. The provisional factory setting is 70%.

ENGLISH

Содержание Optima 300

Страница 1: ...betjeningsvejledning Gebrauchsanweisung User Manual Optima 300 Varmepumpe W rmepumpe Heat pump Version 3 02 0107...

Страница 2: ...1 3 Betriebsmen 20 1 4 Wochenprogramm 25 1 5 Abtauschema 25 1 6 Spezielle Funktionen 26 1 7 Schema f r Sollwerte 27 2 Funktion 2 1 Steuerung Optima 300 28 2 2 Zus tzliche Funktionen 28 2 3 Betriebssic...

Страница 3: ...1 Supply T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling T6 Coil cooling T7 Extract air T8 Antifreeze T9 Solar collector R1 Compressor R3 Pre heat R2 Supp heat R8 Cooling R5 Heat level 2 R1...

Страница 4: ...Min cooling ON To prevent the unit from starting to cool during the winter regardless of how high the room temperature is the set point may be adjusted to the desired minimum outdoor temperature befo...

Страница 5: ...g with the actual unit If the air volumes are set lower than the minimum requirement the heat pump will stop and only pre heated air will be blown from the heat exchanger into all rooms Units without...

Страница 6: ...the week Monday 1 Tuesday 2 Wednesday 3 Thursday 4 Friday 5 Saturday 6 Sunday 7 Clock hour 30 Clock minute 31 Change day 32 Change point Set point Operations menu Exit OK 0 29 Clock hour Adjust the se...

Страница 7: ...ust be set to 0 42 Antifreeze set If freezing water has been switched to ON the set point must be adjusted to the desired temperature at which the freezing water sensor is to stop the unit The tempera...

Страница 8: ...tage to change the temperature difference The difference may be set between 0 1 1 0 52 R9 function This relay may be used as follows If the setting is 0 the relay is off If the setting is 1 the relay...

Страница 9: ...urs Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Wednesday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1...

Страница 10: ...ontrast of the display can be changed by pressing the Info button while the program info screen is displayed Use the arrows to adjust up or down You can also enter menu 44 press OK and then hold the i...

Страница 11: ...20 Room supply extract 0 0 0 0 c 5 0 C 21 Airflow 1 SUP 40 0 100 22 Airflow 2 SUP 70 0 100 23 Airflow 3 SUP 100 0 100 24 Airflow 1 EXT 35 0 100 25 Airflow 2 EXT 55 0 100 26 Airflow 3 EXT 70 0 100 27 C...

Страница 12: ...will perform control in the same way as the electric re heating surface Defrosting When the temperature difference between the temperature upstream of the cooling surface and the temperature of the c...

Страница 13: ...frame and washed in warm soapy water Keep the filter diagonally so the water runs out The filter must not be wrung out or washed in dishwasher After two or three washes replace the flat filter Place...

Страница 14: ...here power in the electric outlet Is the heat pump disconnected through the clock program Has the high pressure switch been activated The cable between the controller and the panel is mounted Has the...

Страница 15: ...oller panel 0V 10V TX RX Motor Valve 24 VDC 0V 0 10V El heater 1 2 Kw Step1 Relay 2 Extra Cooling Upstream Coil 0 8 KW Relay 3 Magnetic valve Defrosting Relay 4 Relay outlet For extra print For El hea...

Страница 16: ...t Air Heat exchanger Supply Air T4 T5 T3 T6 T1 MA4 Compressor T7 Control panel High pressure switch T2 Fresh Air Evaporator cooling coil High pressure switch Condenser heating coil Heat exchanger MA4...

Страница 17: ...ject to Technical Modifications 830209G 160228 Optima 300 8 Flow diagram GE Mini Midi C High pressure switch MA4 Compressor Controller panel MA7 HP Supply air Exhaust air T2 T3 Fresh air Evaporator co...

Страница 18: ...8307 Effretikon Tel 41 0 52 355 11 00 Fax 41 0 52 355 11 05 E Mail info sm heag ch 6 Tyskland Deutschland Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E M...

Отзывы: