.1 Controller Optima 300

Room control:

Room temperature is controlled by room sensor T2, 

which is mounted on the control panel. E.g., if the 

temperature has been set to 21°C, the compressor will 

start when the temperature falls to 20.6°C. When the 

compressor has heated up the room temperature to 

21.4, the compressor will stop. If the compressor cannot 

maintain the room temperature, the motor valve (units 

with water re-heating surface), will begin to control the 

temperature (PID control) when the room temperature 

has fallen to 20°C. 

For units with electric re-heating surface divided into 

four levels, the first level will switch in when the room 

temperature has fallen to 20°C. E.g. if the regulator 

time is set to 3 minutes, the room sensor will wait three 

minutes and then measure whether the room temperature 

is now above or below 20°C, level 2 will switch in. When 

the room temperature eventually reaches 20°C, the 

electric heating levels will begin to switch off at 3 minutes 

interval. If the room temperature rises to 22°C, the by-

pass damper function will regulate to full open, which is 

the temperature start cooling has been set to. If the by-

pass function is ON, the by-pass damper would normally 

open, but if the temperature outside is (T3) 1° C higher 

than the extracted air (T7), then the by-pass damper will 

close to use the “free” cooling of the damper 
To ensure that the by-pass and cooling function does 

not switch in at a too low external temperature, a limit 

temperature of e.g. 15°C may be programmed (point 8 

in the operating menu). When cooling begins, the supply 

and extract air fans will switch to speed 3 and the cooling 

valve MA 7 will open, so that the condenser on the supply 

air side becomes the cooling surface and the cooling 
surface on the escaping air side becomes the condenser. 

When the room temperature has decreased 1° C, the 

compressor hand the fans will return to normal operation. 

The cooling valve MA 7 will not shot down, when the by-

pass function has closed.

If extra cooling equipment is mounted on the unit, this will 

switch in when the room temperature is 2°C higher than 

start cooling. Units with electric pre-heating surface, will 

perform control in the same way as the electric re-heating 

surface.

Defrosting:

When the temperature difference between the 

temperature upstream of the cooling surface and the 
temperature of the cooling surface becomes too large, 

as happens when ice is formed on the cooling surface, 

the unit goes into defrost mode. The magnetic valve 
MA 4 opens and the supply air fan and the electric 
heating surface, stops until the ice has melted and the 
cooling surface has reached a temperature of app. 

5°C (depending on the set point in menu 50). Then the 

magnetic valve closes again and the supply air fan and 
electric heating surface resume operation.

. Extra capacity

Electric element:

If the heating need is larger than the coverage of the VP/

VPC, a supplemental electric element (option) may be set 

to ON in the main menu with a short-cut key.

.3 Operation safety

High pressure switch:

To prevent the compressor exceeding its range of 

application, there is an integral high pressure switch, 

which interrupts when the pressure becomes too large. 

Activate the red reset button once the cause of the error 

has been identified. 

Override control of supply air fan:

If the supply air temperature rises to over 45°C, the 

speed of the supply air fan will begin to rise, in attempt to 

stabilise the supply air temperature at 45°C.

Override control of extract air fan:

If the exhaust air temperature rises to over 45°C in 

cooling mode and the extract air speed at level 3 is 

not set to 100%, the extract air fan will increase speed 

attempt to stabilise the exhaust air temperature at 45°C.

.4 Alarms

Filter timer

To ensure that the filters are changed, and an optimal 

operation is maintained, the controller has a filter timer 

(please se point 14 and 15). When the timer reaches 

the chosen value the display will read “change filter” and 

the red Genvex logo will flash until the filters has been 

changed.

Data error

This error will be shown, if no communication is possible 

between the display and controller. Please control the 

cable connection on the clips 21 – 24.

Frost alert

This error is shown if a water coil is installed in the 

system and the temperature of the water coil is to low. 

Then there is a risk of frost damage. The controller will 

stop the unit and open the valve to the water coil to keep 

the coil warm.

Pressure switch error

When the high pressure switch interrupts, the display will 

read “Pressure switch error” and the red Genvex logo will 

flash until the red reset button is activated.

ENGLISH

Содержание Optima 300

Страница 1: ...betjeningsvejledning Gebrauchsanweisung User Manual Optima 300 Varmepumpe W rmepumpe Heat pump Version 3 02 0107...

Страница 2: ...1 3 Betriebsmen 20 1 4 Wochenprogramm 25 1 5 Abtauschema 25 1 6 Spezielle Funktionen 26 1 7 Schema f r Sollwerte 27 2 Funktion 2 1 Steuerung Optima 300 28 2 2 Zus tzliche Funktionen 28 2 3 Betriebssic...

Страница 3: ...1 Supply T2 Room T3 Fresh air T4 Exhaust air T5 Before coil cooling T6 Coil cooling T7 Extract air T8 Antifreeze T9 Solar collector R1 Compressor R3 Pre heat R2 Supp heat R8 Cooling R5 Heat level 2 R1...

Страница 4: ...Min cooling ON To prevent the unit from starting to cool during the winter regardless of how high the room temperature is the set point may be adjusted to the desired minimum outdoor temperature befo...

Страница 5: ...g with the actual unit If the air volumes are set lower than the minimum requirement the heat pump will stop and only pre heated air will be blown from the heat exchanger into all rooms Units without...

Страница 6: ...the week Monday 1 Tuesday 2 Wednesday 3 Thursday 4 Friday 5 Saturday 6 Sunday 7 Clock hour 30 Clock minute 31 Change day 32 Change point Set point Operations menu Exit OK 0 29 Clock hour Adjust the se...

Страница 7: ...ust be set to 0 42 Antifreeze set If freezing water has been switched to ON the set point must be adjusted to the desired temperature at which the freezing water sensor is to stop the unit The tempera...

Страница 8: ...tage to change the temperature difference The difference may be set between 0 1 1 0 52 R9 function This relay may be used as follows If the setting is 0 the relay is off If the setting is 1 the relay...

Страница 9: ...urs Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Wednesday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Le vel Red T2 1 2 3 4 5 6 7 8 9 10 Friday Hours Minutes Le vel Red T2 1...

Страница 10: ...ontrast of the display can be changed by pressing the Info button while the program info screen is displayed Use the arrows to adjust up or down You can also enter menu 44 press OK and then hold the i...

Страница 11: ...20 Room supply extract 0 0 0 0 c 5 0 C 21 Airflow 1 SUP 40 0 100 22 Airflow 2 SUP 70 0 100 23 Airflow 3 SUP 100 0 100 24 Airflow 1 EXT 35 0 100 25 Airflow 2 EXT 55 0 100 26 Airflow 3 EXT 70 0 100 27 C...

Страница 12: ...will perform control in the same way as the electric re heating surface Defrosting When the temperature difference between the temperature upstream of the cooling surface and the temperature of the c...

Страница 13: ...frame and washed in warm soapy water Keep the filter diagonally so the water runs out The filter must not be wrung out or washed in dishwasher After two or three washes replace the flat filter Place...

Страница 14: ...here power in the electric outlet Is the heat pump disconnected through the clock program Has the high pressure switch been activated The cable between the controller and the panel is mounted Has the...

Страница 15: ...oller panel 0V 10V TX RX Motor Valve 24 VDC 0V 0 10V El heater 1 2 Kw Step1 Relay 2 Extra Cooling Upstream Coil 0 8 KW Relay 3 Magnetic valve Defrosting Relay 4 Relay outlet For extra print For El hea...

Страница 16: ...t Air Heat exchanger Supply Air T4 T5 T3 T6 T1 MA4 Compressor T7 Control panel High pressure switch T2 Fresh Air Evaporator cooling coil High pressure switch Condenser heating coil Heat exchanger MA4...

Страница 17: ...ject to Technical Modifications 830209G 160228 Optima 300 8 Flow diagram GE Mini Midi C High pressure switch MA4 Compressor Controller panel MA7 HP Supply air Exhaust air T2 T3 Fresh air Evaporator co...

Страница 18: ...8307 Effretikon Tel 41 0 52 355 11 00 Fax 41 0 52 355 11 05 E Mail info sm heag ch 6 Tyskland Deutschland Germany Novelan GmbH D 95359 Kasendorf Tel 49 0 92 28 99 60 7 0 Fax 49 0 92 28 99 60 7 189 E M...

Отзывы: