27 - Help function

This function can be used for the following:

Setpoint Function
0

The relay is off.

1

The relay is on when the system is running. 

This can e.g. be used to open and close the 

fresh air damper and the exhaust air damper.

2

The relay is on when extra heat is required or 

when the circulating pump should run when 

heating with water reheating is required.

3

The relay is on when the alarm “Change filter” 

is active. This can be used to activate an 

external alarm.

4

The relay is on when extra cooling is required. 

This function is used if a preheater is also fit-

ted to the system.

5

The control can handle an earth heat exchang-

er by a damper.  

The relay will be on for one of the following 

two conditions:

•  The outdoor temperature, sensor T9, is 

lower than the value configured in item 

26 (frost protection temperature, typi-

cally set at 5 °C).

•  The outdoor temperature, sensor T9, is 

more than 1° above the temperature  

configured in item 1 and 1 ° above the  

current room temperature.

Setting option: between 0 and 5.

28 - System stop

Here you choose if it should be possible to stop the 

system by pressing the key for speed (K1) in the operating 

menu for 3-4 seconds.  If the set point is OFF, the system 

cannot be turned off.

Setting option: ON/OFF

29 - Turn off bypass

To prevent the bypass damper from opening at low fresh 

air temperatures and blow cold, not heated air into the 

dwelling, use this function to configure the lowest fresh air 

temperature,  at which the damper must be closed. The 

value is an expression of the greatest difference that may 

exist between the temperature configured in item 1 and 

the lowest fresh air temperature. 

Setting option: between 0 and 20 °C. If 0°C is selected, the 

function is turned fully off.

30 - Modbus Mode

See separate description for MODBUS.

Setting option: 0-2.

0 = Modbus OFF

1 = 9600 Baud

2 = 19200 Baud

31 - Modbus Adress 

See separate description for MODBUS.

Setting option: 1-247.

 

32 - Humidity max. temperature 

Setting the end point for outside temperature-

compensation (T3), see the X-axis on the graph. 

Setting option: 5-25 °C.

33 - Humidity max. value

Setting the end point for outside temperature 

compensation, see the Y-axis on the graph (desired max. 

humidity value).

Setting option: 35-85 %.

34 - Humidity fan speed 

Setting of how much the fan speed may differ in relation 

to the desired fan speed. See menu points 11, 12, 14 and 

15. 

Setting option: 5-30 %.

35 - Humidity regulating frequency 

Setting of desired frequency for how often the fan speed 

may be changed. 

The function is defined as 1 % per unit of time.

Setting option: 1-60 min.

Sketch for humidity regulation

Desired RH set-point, see the graph below.

Variable fan speed on fresh air, see the graph below.

Extract air

Fresh air

Supply air

Exhaust air

Sensor

location

12   

Содержание OPTIMA 251

Страница 1: ...USER MANUAL OPTIMA 251 PCB ES960C ECO 190 ECO 375...

Страница 2: ...ay menu 8 5 7 Info menu 10 5 8 Service menu 11 5 9 Schedule for week program 12 5 10 Schedule for set points 15 6 Function 16 6 1 Controlling Optima 251 16 6 2 Extra capacity 16 6 3 Operating reliabil...

Страница 3: ...th the control panel there is an access for the A Terminal block Connection to main circuit board Alow currentcable4x0 25mm2 mustbeattachedbetween the unit and the control panel 50 m is the maximum ca...

Страница 4: ...ages menus help texts symbols and collected data logs During the start up procedure the current versions are installed in the control panel so that the control can function without the SD card However...

Страница 5: ...r will not commence even if required K4 Main menu Use this function to enter the main menu and access the sub items Date and time Calendar User menu Display Info operation and Service menu K5 Filter U...

Страница 6: ...er the current hour here When changing between summer and winter time you have to set the time one hour forward or back manually 02 Minutes Enter the current minute here 03 Weekday Enter the current w...

Страница 7: ...nal cooling Setting option ON OFF 03 Reheating If a reheater is fitted to the system it is optional if the reheater should operate If the set point is configured to OFF the heater will not operate eve...

Страница 8: ...from the screen saver to the screen with the symbols for the daily operating options by moving your hand past the control panel If the function is set to OFF press any key to display the daily operati...

Страница 9: ...he password enter a new password in this item and press Enter The password has now been changed 5 7 Info operation The Info operation menu provides an overview of the current operating status of the s...

Страница 10: ...the system must be performed with specialised air measurement equipment and can be performed without the use of the main regulating damper It is not recommended to configure the air flows without exp...

Страница 11: ...Menu item 1 the bypass damper will begin to open The bypass is 100 open when the temperature reaches the set point in the User Menu Item 1 the temperature differential set in this menu item To get a...

Страница 12: ...event the bypass damper from opening at low fresh air temperatures and blow cold not heated air into the dwelling use this function to configure the lowest fresh air temperature at which the damper mu...

Страница 13: ...he fan speed may differ in relation to the desired fan speed Example Set point 34 15 With a desired fan speed of 3 the fan speed will be able to fluctuate 15 Since fan speed 3 is set at 75 in service...

Страница 14: ...required 40 Reheat offset Offset for reheater with reference to the setpoint requested temp on display user menu 01 e g requested temp 20 C offset value 2 reheater aims for 18 C supply temperature 41...

Страница 15: ...ours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3...

Страница 16: ...8 Filter stop OFF ON OFF 19 Method of regulation 2 0 2 20 Preheating 3 C 15 0 C 21 By pass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduct...

Страница 17: ...e temperature set the reheating will keep running When the temperature reaches the value set the electrical reheater will disconnect Electrical reheater modulating For systems with the modulating elec...

Страница 18: ...r if necessary Plastic exchanger No cleaning with solvents use only clean water carefully only careful dust removal from air intake surfaces with a household vacuum cleaner Fans Inspect the two fan wh...

Страница 19: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Страница 20: ...At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All Genve...

Отзывы: