10   

The alarm will read OFF when the error has been corrected 

or the filter is changed and reset.

Alarm

Status Error at ”ON”

Control 

stopped

ON/

OFF

Filter not changed after 14 days/ 

Frost protection error/The system 

is equipped with an external switch 

between terminals 28 and 29. 

“Alarm” will be displayed when 

these are short-circuited and the 

system has stopped. 

Change 

filter

ON/

OFF

The filters should be changed.

Frost 

protection

ON/

OFF

The temperature of the water after 

heater is too low (frost danger).

Com error ON/

OFF

The control panel cannot 

communicate with the main board 

between display and printed circuit 

board).

Hour counters (2 pages)

Press “Arrow down” again to display the hour counters, 

which count from the day the system is put into operation. 

The figures shown should be multiplied by 10. This shows 

how many hours the system has been running, how many 

hours the system has run at the various speeds and how 

many hours the relays have been connected (ON).

Total tid
Level 

0

Level 

1

Level 

2

Level 

3

Level 

4

Relay 2 Reheating
Relay 3 Preheating
Relay 8 System in operation
Relay 9 Help function

Press “Exit” to return to the main menu.

5.8 Service menu 

Use this function to configure the following sub-menu 

items.

   

10 - Level 1 Supply air

Level 1, which is the lowest speed, is usually used when 

there is nobody home. Both fans can be configured 

independently of each other for all levels so that the air 

flow in the supply air and in the extract air is equal, which 

provides optimal operation. 

The adjustment of the system must be performed with 

specialised air measurement equipment and can be 

performed without the use of the main regulating damper.  

It is not recommended to configure the air flows without 

expert advice. Incorrect configuration can lead to major 

energy consumption or unpleasant indoor climate. 

Setting option: between 0 and 100 %.

11 - Level 2 Supply air

Level 2 is the recommended speed of the system in order 

to provide the optimal indoor climate and it should be  

adjusted to the ventilation requirement of the dwelling.

Setting option: between 0 and 100 %.

12 - Levels 3 and 4 Supply air

Level 3 is the highest speed that can be configured. It is 

used e.g. if there are many guests or there is a lot of  

activity in the kitchen.

Setting option of level 3: between 0 and 100 %.

Factory setting of level 3: 75 %.

Level 4 is used mainly in summer to lower the indoor 

temperature. Remember that a higher air exchange rate 

increases the energy consumption.

Setting option of level 4: cannot be configured.

13 - Level 1 Extract air

The fan speed is adjusted until the same air flow is 

achieved as the supply air on level 1.

Setting option: between 0 and 100 %.

14 - Level 2 Extract air

The fan speed is adjusted until the same air flow is 

achieved as the supply air on level 2.

Setting option: between 0 and 100 %.

15 - Levels 3 and 4 Extract air

The air flow of level 3 is adjusted to the same air flow as 

the supply air on levels 3 and 4 (item 12).

Setting option of level 3: between 0 and 100 %.

Factory setting of level 3: 75 %.

Setting option of level 4: cannot be configured.

16 - Fine tuning (T2)

It is possible to fine tune the room sensor of the control 

panel so the correct current room temperature is 

displayed.  

Setting option: between -5  and 0 °C.

Содержание OPTIMA 251

Страница 1: ...USER MANUAL OPTIMA 251 PCB ES960C ECO 190 ECO 375...

Страница 2: ...ay menu 8 5 7 Info menu 10 5 8 Service menu 11 5 9 Schedule for week program 12 5 10 Schedule for set points 15 6 Function 16 6 1 Controlling Optima 251 16 6 2 Extra capacity 16 6 3 Operating reliabil...

Страница 3: ...th the control panel there is an access for the A Terminal block Connection to main circuit board Alow currentcable4x0 25mm2 mustbeattachedbetween the unit and the control panel 50 m is the maximum ca...

Страница 4: ...ages menus help texts symbols and collected data logs During the start up procedure the current versions are installed in the control panel so that the control can function without the SD card However...

Страница 5: ...r will not commence even if required K4 Main menu Use this function to enter the main menu and access the sub items Date and time Calendar User menu Display Info operation and Service menu K5 Filter U...

Страница 6: ...er the current hour here When changing between summer and winter time you have to set the time one hour forward or back manually 02 Minutes Enter the current minute here 03 Weekday Enter the current w...

Страница 7: ...nal cooling Setting option ON OFF 03 Reheating If a reheater is fitted to the system it is optional if the reheater should operate If the set point is configured to OFF the heater will not operate eve...

Страница 8: ...from the screen saver to the screen with the symbols for the daily operating options by moving your hand past the control panel If the function is set to OFF press any key to display the daily operati...

Страница 9: ...he password enter a new password in this item and press Enter The password has now been changed 5 7 Info operation The Info operation menu provides an overview of the current operating status of the s...

Страница 10: ...the system must be performed with specialised air measurement equipment and can be performed without the use of the main regulating damper It is not recommended to configure the air flows without exp...

Страница 11: ...Menu item 1 the bypass damper will begin to open The bypass is 100 open when the temperature reaches the set point in the User Menu Item 1 the temperature differential set in this menu item To get a...

Страница 12: ...event the bypass damper from opening at low fresh air temperatures and blow cold not heated air into the dwelling use this function to configure the lowest fresh air temperature at which the damper mu...

Страница 13: ...he fan speed may differ in relation to the desired fan speed Example Set point 34 15 With a desired fan speed of 3 the fan speed will be able to fluctuate 15 Since fan speed 3 is set at 75 in service...

Страница 14: ...required 40 Reheat offset Offset for reheater with reference to the setpoint requested temp on display user menu 01 e g requested temp 20 C offset value 2 reheater aims for 18 C supply temperature 41...

Страница 15: ...ours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3...

Страница 16: ...8 Filter stop OFF ON OFF 19 Method of regulation 2 0 2 20 Preheating 3 C 15 0 C 21 By pass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduct...

Страница 17: ...e temperature set the reheating will keep running When the temperature reaches the value set the electrical reheater will disconnect Electrical reheater modulating For systems with the modulating elec...

Страница 18: ...r if necessary Plastic exchanger No cleaning with solvents use only clean water carefully only careful dust removal from air intake surfaces with a household vacuum cleaner Fans Inspect the two fan wh...

Страница 19: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Страница 20: ...At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All Genve...

Отзывы: