36 - Not applicable

37 - Preheat PI P

P-band for the PI controller for the electrical modulating

preheater.

The P-band controls the amplification of the controller 

following a deviation from the setpoint (speeder)

38 - Preheat PI I

I-band for the PI controller for the electrical modulating

preheater.

The function controls how quickly the controller adapts to 

a deviation of the setpoint (brake).

39 - Preheat Reg

Preheat Cycle the function works the following way

e.g. necessary output 50% and cycle =60 sec means 

controller will switch on preheater for 30 sec and off for 

30 sec.

Note: please refer to your country specifik regulations on 

limitations when adjusting this function.

The modulating preheater function refers to the value 

adjusted in setpoint no. 20.

The preheater will try to maintain a steady fresh air 

temperature according to this setpoint.

When using the modulating preheater - the exsting fresh 

air temperature sensor (T3) built into the ventilation unit 

can be used as reference. No extra temperatur sensor is 

required.

40 - Reheat offset 

Offset for reheater with reference to the setpoint 

requested temp on display (user menu 01) 

e.g. requested temp = 20 °C

offset value=2 reheater aims for 18 °C supply temperature

41 - Reheat PI P

P-band for the PI controller for the electrical modulating

reheater.

The P-band controls the amplification of the controller 

following a deviation from the setpoint (speeder).

42 - Reheat PI I

I-band for the PI controller for the electrical modulating

reheater.

The function controls how quickly the controller adapts to 

a deviation of the setpoint (brake).

43 - Reheat Reg

Reheat Cycle the function works the following way

e.g. necessary output 50% and cycle = 60 sec means 

controller will switch on preheater for 30 sec and off for 

30 sec.

Note: please refer to your country specifik regulations on 

limitations when adjusting this function.

The modulating reheater function refers to the value 

adjusted in setpoint no. 40.

The reheater will try to maintain a steady supply air 

temperature according to this setpoint.

When using the modulating reheater - it will be necessary 

to replace the inlet air temperature sensor (T1) in the 

ventilation unit with a new temperature sensor installed 

upstream of the reheater.

 

14   

Содержание OPTIMA 251

Страница 1: ...USER MANUAL OPTIMA 251 PCB ES960C ECO 190 ECO 375...

Страница 2: ...ay menu 8 5 7 Info menu 10 5 8 Service menu 11 5 9 Schedule for week program 12 5 10 Schedule for set points 15 6 Function 16 6 1 Controlling Optima 251 16 6 2 Extra capacity 16 6 3 Operating reliabil...

Страница 3: ...th the control panel there is an access for the A Terminal block Connection to main circuit board Alow currentcable4x0 25mm2 mustbeattachedbetween the unit and the control panel 50 m is the maximum ca...

Страница 4: ...ages menus help texts symbols and collected data logs During the start up procedure the current versions are installed in the control panel so that the control can function without the SD card However...

Страница 5: ...r will not commence even if required K4 Main menu Use this function to enter the main menu and access the sub items Date and time Calendar User menu Display Info operation and Service menu K5 Filter U...

Страница 6: ...er the current hour here When changing between summer and winter time you have to set the time one hour forward or back manually 02 Minutes Enter the current minute here 03 Weekday Enter the current w...

Страница 7: ...nal cooling Setting option ON OFF 03 Reheating If a reheater is fitted to the system it is optional if the reheater should operate If the set point is configured to OFF the heater will not operate eve...

Страница 8: ...from the screen saver to the screen with the symbols for the daily operating options by moving your hand past the control panel If the function is set to OFF press any key to display the daily operati...

Страница 9: ...he password enter a new password in this item and press Enter The password has now been changed 5 7 Info operation The Info operation menu provides an overview of the current operating status of the s...

Страница 10: ...the system must be performed with specialised air measurement equipment and can be performed without the use of the main regulating damper It is not recommended to configure the air flows without exp...

Страница 11: ...Menu item 1 the bypass damper will begin to open The bypass is 100 open when the temperature reaches the set point in the User Menu Item 1 the temperature differential set in this menu item To get a...

Страница 12: ...event the bypass damper from opening at low fresh air temperatures and blow cold not heated air into the dwelling use this function to configure the lowest fresh air temperature at which the damper mu...

Страница 13: ...he fan speed may differ in relation to the desired fan speed Example Set point 34 15 With a desired fan speed of 3 the fan speed will be able to fluctuate 15 Since fan speed 3 is set at 75 in service...

Страница 14: ...required 40 Reheat offset Offset for reheater with reference to the setpoint requested temp on display user menu 01 e g requested temp 20 C offset value 2 reheater aims for 18 C supply temperature 41...

Страница 15: ...ours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3...

Страница 16: ...8 Filter stop OFF ON OFF 19 Method of regulation 2 0 2 20 Preheating 3 C 15 0 C 21 By pass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduct...

Страница 17: ...e temperature set the reheating will keep running When the temperature reaches the value set the electrical reheater will disconnect Electrical reheater modulating For systems with the modulating elec...

Страница 18: ...r if necessary Plastic exchanger No cleaning with solvents use only clean water carefully only careful dust removal from air intake surfaces with a household vacuum cleaner Fans Inspect the two fan wh...

Страница 19: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Страница 20: ...At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All Genve...

Отзывы: