Duct connection
All duct connections are marked with a yellow sticker
indicating the type of ventilation duct to be connected.
Connect the supply air
Duct system from the unit to the supply outlet in the living
area.
Connect the extract air
Duct system from wet rooms to the unit.
Connect the fresh air
Duct system from fresh air roof cowls/external grills from
or the ground collector to the unit.
Connect the exhaust air
Duct system from unit to the escaping roof cowls/external
grills.
Optimal operation is achieved by mounting a
connector piece Ø160 mm with double sealing lips
mm in each outlet of the ECO 375 TS/TL.
Condensate drain
The units produce up to 6 litres of condensate per day. It is
therefore important that the condensate drain is correctly
executed and that the unit has a slight slope towards the
drain gully.
A standard Ø32 mm plumbers siphon can be connected
directly on to the ventilation unit.
From the siphon and to the drain gully there must be a
necessary slope at 1%.
If the unit is installed in a cold loft space, the condensate
drain pipe must be insulated to prevent freezing of the
condensate in the pipe. However, it is recommended that
the siphon is installed in a heated space below to ensure
that the water in it does not freeze.
If installation problems make it impossible to secure the
condensate drain pipe from freezing by insulation, it will be
necessary to mount a thermostat-controlled heating tape
round the condensate drain pipe.
During operating there will be an underpressure
in the unit it will therefor be neccesary to install
a watertrap/siphon with a minimum of 50 mm
watercolumn