background image

18   

DECLARATION OF CONFORMITY

Declaration of conformity can be downloaded at www.genvex.com.

Содержание ECO 375 TL

Страница 1: ...INSTALLATION MANUAL ECO 375 TS TL Mechanical ventilation with passive heat recovery A...

Страница 2: ...e supply air 7 Electrical installation 8 Inspection and initial adjustment of appliance 8 Optimum initial adjustment of plant 8 Maintenance of ventilation unit 9 Spare parts 11 Trouble shooting 12 Saf...

Страница 3: ...t and 300 mm below the unit for access to condensate drain and siphon ECO 375 TS TL is supplied in a vertical version as shown below Weight 40 kg KVM Genvex A S recommends that you always carefully pl...

Страница 4: ...mounting vertical 1 Before fixing the mounting bracket to the wall please ensure that the bracket is installed in the correct orientation A small cut in the center of the bracket indicate the center t...

Страница 5: ...portant that the condensate drain is correctly executed and that the unit has a slight slope towards the drain gully A standard 32 mm plumbers siphon can be connected directly on to the ventilation un...

Страница 6: ...ance between air intake and exhaust 1 meter Insulation of ducts in cold loft spaces In order to exploit the unit s high recovery potential efficiency it is necessary to insulate the ducts correctly Ge...

Страница 7: ...or electrical reheating surface can be mounted for reheating the supply air up to room temperature Water based reheating surface To protect the water based reheating surface from frost burst a frost p...

Страница 8: ...e unit can be carried out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is correctly mounted with water trap and is protected from freezing Pour...

Страница 9: ...clean change the filters Switch the unit off on the switch on the control panel or the switch on the electrical panel Open the front doors and remove the filters When the filters have been cleaned re...

Страница 10: ...ese are very fragile Broken lamellars will result in lower heat recovery rates and higher pressure drop through the heat exchanger Fans Check the two fan wheels for dirt If they are dirty they may be...

Страница 11: ...eatexchanger Aluminium 069231 069235 069218 G4 069222 M5 069223 F7 069224 G4 069222 069214 TS 069282 TL 069285 069178 069237 069252 069219 060535 Optima 251 042478 Optima 260 042479 069209 ALU 069210...

Страница 12: ...extract air fi lter Fuse on the circuit board is blown Cold supply air Possible error Clogged heat changer Faulty extract air fan Clogged extract air filter Electrical reheater is disconnected at the...

Страница 13: ...CO2 L2 Optima Display L3 Sensors T1 T3 T4 T7 L4 Humidity sensor P1 Demand CTRL B1 L6 Sensors T8 T9 L8 External stop L10 Modulating Pre Reheating L11 0 10V Motorvalve Reheating 0 10V Belimo LM230ASR b...

Страница 14: ...3 Max load total 1800W Aux relay R9 1x230V 50Hz ONLY control current Sensor Frost Sensor extract air Sensor exhaust air Sensor fresh air Sensor supply air Sensor Option External stop EC fan Extract ai...

Страница 15: ...nsors T1 T3 T4 T7 L4 Humidity sensor P1 Demand CTRL B1 L5 Room sensor T2 optional L6 Option 1 2 Sensors T8 T9 L7 Option 1 L8 External stop L10 Modulating Pre Reheating Option 2 L11 0 10V Motorvalve Re...

Страница 16: ...otal 1800W Aux relay R9 1x230V 50Hz ONLY control current Sensor Frost Sensor extract air Sensor exhaust air Sensor fresh air Sensor supply air Sensor Optional for aux relay R9 External stop EC fan Ext...

Страница 17: ...L2 21 22 23 24 21 22 23 24 Option 1 Option 2 12V 12V 0V 0V 2V 0V 0V 2V 2V 2V 2V 3V 3V 3V 3V 0V Option 3 0V 10V Optima Design Connection for OPT 100 OPUS control panel Connection for boost button and f...

Страница 18: ...18 DECLARATION OF CONFORMITY Declaration of conformity can be downloaded at www genvex com...

Страница 19: ...19 DISASSEMBLY INSTRUCTIONS Remove filters Remove counterflow heat exchanger Remove fan Remove bypass actuator...

Страница 20: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: