IMPORTANT:

 

When installing the ECO 375 follow these instructions:

1) Turn off the electricity before opening the unit
2)  Install an air tight water trap on a non-freezing location 

to compensate for the fan pressure.

3)  The height of the water trap must be at least 50 mm.
4)  Make sure that the drain flows downwards all the way 

from the unit.

5)  Pour 1 liter water into the drip tray of the unit to verify 

that it is drained properly. Before each heating season 

make sure that the drain is filled with water. 

6)  If freezing of the water trap occurs, it is necessary to 

install a thermostat and electrical heater to prevent 

freezing when the temperature drops below +2 °C.

7) Air flow adjustments must be made on both supply 

and exhaust air sides before use of the machine. It is 

important supply and exhaust air volumes are balanced.

8)  It is recommended to keep the ducts closed until the unit 

is started and the system is adjusted.

These instructions must be followed. If the condensate 

drain is not made according to this instruction, Genvex can 

not be made responsible for any additional damages, which 

have nothing to do with the Genvex unit.

Dimensions drawing (in mm) 

To allow access for service and maintenance, there must be 

a clear space of a minimum of 600 mm in front of the unit 

and 300 mm. below the unit (for access to condensate drain 

and siphon)

ECO 375 TS/TL is supplied in a vertical version  (as shown 

below).

Weight: 40 kg

KVM-Genvex A/S recommends that you always carefully 

plan the installation location of your Genvex product in re- 

lation to the location of certain rooms. This is a technical 

product featuring fans and/or a heating pump which – in 

certain rare cases, in combination with inexpedient instal-

lation conditions – may result in dissatisfactory noise or 

vibration disturbances. As a main rule, we recommend 

that technical installations never be mounted right next 

to a bedroom. At the same time, we recommend that when 

your Genvex installation is fastened to the structure 

of the building, this is done to a heavy structure, e.g. 

concrete. Like-wise, you should also ensure that there is 

no transmission of noise or vibrations through materials 

that are in contact with the installation. If there is a risk of 

transmission of noise and vibrations, we recommend that 

you install additional vibration-damping materials and 

soundproof the installation room.

  1.  Fresh air
  2.  Extract air (from building)
  3.  Exhaust air (to outside)
  4.  Supply air
  5.  Heat exchanger
  6.  Supply air fan
  7.  Extract air fan
  8.  Filter fresh air
  9.  Filter exhaust air
10.  Electrical connection
11.  Condensation tray
12.  Condensation drain

 

 595 

 307,4 

 307,4 

 172,2 

 278 

 143,5 

161x 4 

A

1

2

3

4

 600 

 944 

DETAIL A

SCALE 1 : 5

13

Electronic

Connection

 179 

5

6

7

8-9

10

11-12

Lokation:

 

 

 3

INSTALLATION

Содержание ECO 375 TL

Страница 1: ...INSTALLATION MANUAL ECO 375 TS TL Mechanical ventilation with passive heat recovery A...

Страница 2: ...e supply air 7 Electrical installation 8 Inspection and initial adjustment of appliance 8 Optimum initial adjustment of plant 8 Maintenance of ventilation unit 9 Spare parts 11 Trouble shooting 12 Saf...

Страница 3: ...t and 300 mm below the unit for access to condensate drain and siphon ECO 375 TS TL is supplied in a vertical version as shown below Weight 40 kg KVM Genvex A S recommends that you always carefully pl...

Страница 4: ...mounting vertical 1 Before fixing the mounting bracket to the wall please ensure that the bracket is installed in the correct orientation A small cut in the center of the bracket indicate the center t...

Страница 5: ...portant that the condensate drain is correctly executed and that the unit has a slight slope towards the drain gully A standard 32 mm plumbers siphon can be connected directly on to the ventilation un...

Страница 6: ...ance between air intake and exhaust 1 meter Insulation of ducts in cold loft spaces In order to exploit the unit s high recovery potential efficiency it is necessary to insulate the ducts correctly Ge...

Страница 7: ...or electrical reheating surface can be mounted for reheating the supply air up to room temperature Water based reheating surface To protect the water based reheating surface from frost burst a frost p...

Страница 8: ...e unit can be carried out 3 Check that filters are clean may be dirty from installation work 4 Check that the condensate drain is correctly mounted with water trap and is protected from freezing Pour...

Страница 9: ...clean change the filters Switch the unit off on the switch on the control panel or the switch on the electrical panel Open the front doors and remove the filters When the filters have been cleaned re...

Страница 10: ...ese are very fragile Broken lamellars will result in lower heat recovery rates and higher pressure drop through the heat exchanger Fans Check the two fan wheels for dirt If they are dirty they may be...

Страница 11: ...eatexchanger Aluminium 069231 069235 069218 G4 069222 M5 069223 F7 069224 G4 069222 069214 TS 069282 TL 069285 069178 069237 069252 069219 060535 Optima 251 042478 Optima 260 042479 069209 ALU 069210...

Страница 12: ...extract air fi lter Fuse on the circuit board is blown Cold supply air Possible error Clogged heat changer Faulty extract air fan Clogged extract air filter Electrical reheater is disconnected at the...

Страница 13: ...CO2 L2 Optima Display L3 Sensors T1 T3 T4 T7 L4 Humidity sensor P1 Demand CTRL B1 L6 Sensors T8 T9 L8 External stop L10 Modulating Pre Reheating L11 0 10V Motorvalve Reheating 0 10V Belimo LM230ASR b...

Страница 14: ...3 Max load total 1800W Aux relay R9 1x230V 50Hz ONLY control current Sensor Frost Sensor extract air Sensor exhaust air Sensor fresh air Sensor supply air Sensor Option External stop EC fan Extract ai...

Страница 15: ...nsors T1 T3 T4 T7 L4 Humidity sensor P1 Demand CTRL B1 L5 Room sensor T2 optional L6 Option 1 2 Sensors T8 T9 L7 Option 1 L8 External stop L10 Modulating Pre Reheating Option 2 L11 0 10V Motorvalve Re...

Страница 16: ...otal 1800W Aux relay R9 1x230V 50Hz ONLY control current Sensor Frost Sensor extract air Sensor exhaust air Sensor fresh air Sensor supply air Sensor Optional for aux relay R9 External stop EC fan Ext...

Страница 17: ...L2 21 22 23 24 21 22 23 24 Option 1 Option 2 12V 12V 0V 0V 2V 0V 0V 2V 2V 2V 2V 3V 3V 3V 3V 0V Option 3 0V 10V Optima Design Connection for OPT 100 OPUS control panel Connection for boost button and f...

Страница 18: ...18 DECLARATION OF CONFORMITY Declaration of conformity can be downloaded at www genvex com...

Страница 19: ...19 DISASSEMBLY INSTRUCTIONS Remove filters Remove counterflow heat exchanger Remove fan Remove bypass actuator...

Страница 20: ...ilies At the same time our system is an important element when it comes to saving energy in homes and in society as a whole in fact you can recover up to 95 of the heat energy with a Genvex system All...

Отзывы: