Condensate drain
When changing the filter in August/September, before
outside temperatures falls to 5°C, check the condensate
drain for blockage by dirt and check that there is water in
the water trap.
Pour 1 litre water into the condensate tray and make sure it
can run off without problems. If the condensate drain does
not work, this could lead to water damage in the dwelling.
Countercurrent heat exchanger
Inspect the countercurrent heat exchanger. If it is dirty,
remove it and wash in warm soapy water and then rinse,
possibly in the bathroom using the shower head.
When taking out the heatexchanger – please be carefull
not to touch the lamellars ,as these are very fragile. Broken
lamellars will result in lower heat recovery rates and higher
pressure drop through the heat exchanger.
Fans
Check the two fan wheels for dirt. If they are dirty they may
be cleaned with a brush, bottle washer etc. Remember to
disconnect the power supply to the ventilation unit.
By demounting the front it is important to remove the
filters before the front is removed.
Supply and extract valves
Clean the valves by wiping with a dry cloth. Make sure the
valve does not rotate, causing a change in the air volume.
Important:
When reinstalling the front plate to the
ventilation unit please make sure not to use electrical
tools for tightning the bolts as this could possibly result
in damage to the threaded connections.
Gently tighten alle the frontplate bolts untill the frontplate
is securely fixed to the ventilation unit cabinet.