2.1 Installation of the Control Panel
The control panel is designed for being mounted to an Opus
type power socket.
2.2 Installation
Find the installation place for the control panel,
connect the wires and click the control panel into place.
Fit a 8 x 0.25 mm
2
low-current cable between the
ventilation unit print circuit board and the control panel.
The maximum cable length is 50 m.
The voltage drop for cable lengths over 50 m is too high and
can cause operating errors.
Check that the low-current cable is connected to the same
numbers at both ends. (Between the control panel and the
main circuit board in the unit.)
The key on the left of the control panel is K3, and the key on
the right of the control panel is K5.
2. INSTALLATION OF OPTIMA 100 OPUS