19
8. TABLE OF FACTORY SETTINGS
Item Headline
Factory setting
Configuration area
Date
Date
Date
Date
(5.5) 01 Temperature
21°C
10 - 30°C
02 Preheating
OFF
ON/OFF
03 Reheating
OFF
ON/OFF
04 Timer levels 3 and 4
OFF
ON/OFF
05 Change filter
3 months
1 - 12 months
06 Humidity control
OFF
ON/OFF
(5.8) 10 Level 1 Supply air
30%
0 - 100%
11 Level 2 Supply air
50%
0 - 100%
12 Level 3 and 4 Supply air
75%
0 - 100%
13 Level 1 Extract air
30%
0 - 100%
14 Level 2 Extract air
50%
0 - 100%
15 Level 3 and 4 Extract air
75%
0 - 100%
16 Not applicable
OFF
÷ 5 - 0°C
17 Timer levels 3 and 4
3 hours
1 - 9 hours
18 Filter/stop
OFF
ON/OFF
19 Method of regulation
2
0 - 2
20 Preheating
÷ 3°C
÷ 15 - 0°C
21 Bypass open
3°C
1 - 10°C
22 Regulation water
20 sec.
1 - 250 sec.
23 Regulation electricity
3 min.
1 - 30 min.
24 Frost reduction
0°C
0 - 10°C
25 Frost protection
OFF
ON/OFF
26 Frost protection temperature
5°C
0 - 10°C
27 Help functions
0
0 - 5
28 System stop
OFF
ON/OFF
29 Turn off bypass
4°C
0 - 20°C
30 Modbus Mode
2
0 - 2
31 Modbus Address
1
1 - 247
32 Humidity max. temperature
15°C
5 - 25°C
33 Humidity max. value
60%
35 - 85%
34 Humidity fan speed
15%
5 - 30%
35 Humidity regulating frequency
10 min.
1 - 60 min.
36 Right/Left
0
0-1
37 Preheat PI P
5
1-255
38 Preheat PI I
200
1-255
39 Preheat Reg
40
10-120
40 Reheat offset
-2
0-20
41 Reheat PI P
5
1-255
42 Reheat PI I
200
1-255
43 Reheat Reg
40
10-120
44 Display Model
1
0-2
45 Boost time 1 (min)
15
0-250
46 Boost time 2 (min)
30
0-250
47 Boost time 3 (min)
60
0-250
48 Calendar on/off
0
0-1