27 – Help function

This function can be used for the following:

Set point Function
0

The relay is off.

1

The relay is on when the system is running.  

This can, e.g. be used to open and close  

the outdoor air damper and the discharge  

air damper.

2

The relay is on when extra heat is required or 

when the circulating pump should run when 

heating with water reheating is required.

3

The relay is on when the “Change filter” alarm 

is active. This can be used to activate an 

external alarm.

4

The relay is on when extra cooling is required. 

This function is used if a preheater is also 

fitted to the system.

5

The control can handle an earth heat 

exchanger using a damper.  

The relay will be on if one of the following two 

conditions are met:

•  The outdoor temperature, sensor T9, is 

lower than the value configured in item 26 

(frost protection temperature, typically set 

at 5°C).

•  The outdoor temperature, sensor T9, 

is more than 1° above the temperature 

configured in item 1 and 1 ° above the 

current room temperature.

Setting option: between 0 and 5.

28 – System stop

Here you choose if it should be possible to stop the system 

by pressing the key for speed (K1) in the operating menu for 

3-4 seconds. If the set point is OFF, the system cannot be 

turned off.

Setting option: ON/OFF

29 – Turn off bypass

To prevent the bypass damper from opening at low outdoor 

air temperatures and from blowing cold, unheated air into 

the dwelling, use this function to configure the lowest 

outdoor air temperature, at which the damper must be 

closed. The value is an expression of the greatest 

difference that may exist between the temperature 

configured in item 1 and the lowest outdoor air 

temperature. 

Setting option: Between 0 and 20 °C. If 0°C is selected,  

the function is turned completely off.

30 – Modbus Mode

See separate description for MODBUS.

Setting option: 0-2.

 

0 = Modbus OFF

1 = 9600 Baud

2 = 19200 Baud

31 – Modbus Address 

See separate description for MODBUS.

Setting option: 1-247.

 

32 – Humidity max. temperature 

Setting the end point for outside temperature-

compensation (T3), see the X-axis on the graph. 

Setting option: 5-25°C.

33 – Humidity max. value

Setting the end point for outside temperature 

compensation, see the Y-axis on the graph (desired max. 

humidity value).

Setting option: 35-85%.

34 – Humidity fan speed 

Setting of how much the fan speed may differ in relation to 

the desired fan speed. See menu items 11, 12, 14 and 15. 

Setting option: 5-30%.

Examples 

Set point 34 = ± 15%

With a desired fan speed of 3, the fan speed will be able to 

fluctuate by ± 15%. Since fan speed 3 is set at 75% in 

Service Menu 12 and 15, the fan speed will be max. 90% 

and min. 60%.

The same applies to fan speed 2. Since fan speed 2 is set at 

50% in Service Menu 11 and 13, the fan speed will be max. 

65% and min. 35%.

Fan speed is regulated by ±1% once every 10 min.

Setting option: See item 35

Содержание ECO 190

Страница 1: ...OPERATING INSTRUCTIONS OPTIMA 260 ECO 190 ECO 375...

Страница 2: ...TENTS 1 Installation of Optima 100 Design 3 2 Installation of Optima 100 Opus 4 3 Operation 5 4 Data Logger 5 5 Genlog Set Points 9 6 Function 16 7 Maintenance 17 8 Troubleshooting 18 9 Table of Facto...

Страница 3: ...point Support point Underneath the control panel there is access for the A Terminal block Connection to main circuit board Fit a 8 x 0 25 mm2 low current cable between the unit and the control panel T...

Страница 4: ...able between the ventilation unit print circuit board and the control panel The maximum cable length is 50 m The voltage drop for cable lengths over 50 m is too high and can cause operating errors Che...

Страница 5: ...in order to take advantage of the automatic data logging feature The latest version of the Genvex Genlog software can be ordered from Genvex by telephone 45 73532700 1 2 3 4 K3 K5 All Genvex ventilati...

Страница 6: ...seful if you want to refer to a certain logging There is an area with grey and white lines at the top of the logging area itself on the screen These lines will be red if relay function is active Hold...

Страница 7: ...or monitoring only Data from Control System Set points in control system Opens the following box Here it is possible to retrieve all set points from the microchip or control panel change them and then...

Страница 8: ...for the data logger General setup Here you can choose language model as well as folder for the log files For instance it can be a good idea to create a folder for logs under Documents and set up the p...

Страница 9: ...ay These days can be filled in individually in the same way as under the example for Monday User menu 01 Temperature Set your desired temperature between 10 and 30 C Item 19 of the Service menu allows...

Страница 10: ...or energy consumption or unpleasant indoor climate Setting option between 0 and 100 11 Level 2 Supply air Level 2 is the recommended speed of the system for providing optimal indoor climate It should...

Страница 11: ...ith on off bypass e g ECO190 ECO 375 The bypass opens when the temperature reaches the set point in User Menu item 1 the temperature differential set in this menu item Setting option between 1 and 10...

Страница 12: ...mper from opening at low outdoor air temperatures and from blowing cold unheated air into the dwelling use this function to configure the lowest outdoor air temperature at which the damper must be clo...

Страница 13: ...n 1 25 13 35 Humidity regulating frequency Setting of desired frequency for how often the fan speed may be changed The function is defined as 1 per unit of time When humidity regulation is activated t...

Страница 14: ...to maintain a supply temperature of 18 C 41 Reheat PI P P band for the PI controller for the electrical modulating reheater The P band controls the amplification of the controller following a deviati...

Страница 15: ...rs Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Thursday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Sunday Hours Minutes Speed Red T2 1 2 3 4 5 6 7 8 9 10 Tuesday Hours Minutes Speed Red T2 1 2 3 4...

Страница 16: ...sion For systems with electrical reheaters the reheater will connect when the temperature has fallen 1 C below the set temperature If the regulation time is set to e g 3 minutes temperature sensorT1 w...

Страница 17: ...runs off freely If the condensation drain does not work this could lead to water damage at your home Heat exchanger Inspect the heat exchanger every year If it is dirty remove it and Alu exchanger Was...

Страница 18: ...gram Filter timer has switched the system off Condensed water is leaking from the unit Possible error Condensation outlet blocked by dirt The condensation outlet is not adequately protected against fr...

Страница 19: ...ing 3 C 15 0 C 21 Bypass open 3 C 1 10 C 22 Regulation water 20 sec 1 250 sec 23 Regulation electricity 3 min 1 30 min 24 Frost reduction 0 C 0 10 C 25 Frost protection OFF ON OFF 26 Frost protection...

Страница 20: ...t home and in society as a whole a Genvex system actually allows you to recover up to 95 of the heat energy All Genvex systems have energy label A An original Genvex system is built by skilled experie...

Отзывы: