GEC24, GES24, GEH24 GEC3-24 & GES3-24 SERIES

ANSI/UL & CAN/ULC COMPLIANT

GECA24, GESA24, GECB24, GESB24, GECG24,

GESG24, GECR24 & GESR24, WGEC24, WGES24

WGECA24, WGESA24, WGECB24, WGESB24,

WGECG24, WGESG24, WGECR24 & WGESR24 SERIES

ANSI/UL & CAN/ULC COMPLIANT

VISIBLE AND/OR AUDIBLE 

SIGNALING APPLIANCES

I. INTRODUCTION

The Gentex models GEC24, GES24, GEH24, GEC3-24, GES3-24, WGEC24, WGES24, GECA24, GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24, WGECA24,

WGESA24, WGECB24, WGESB24, WGECG24, WGESG24, WGECR24, WGESR24 are high quality audible and/or visible signaling appliances.  The high intensity strobe utilizes a Xenon flash

tube that generates a high-intensity flash visible from all angles.  This appliance is intended to provide a visible, audible or audible/visible, depending on the model, notification signal for the 

purpose of life safety and property protection.  The GEC3-24, GES3-24, GECA24, GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24 are provided with a slider switch which

allows for candela selection at the installation site; the candela intensities which can be selected are 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd (24VDC only).  The GEC24 and GES24 are fixed 

candela units; the candela intensities which can be ordered, are 177Cd and 15/75Cd.  The WGEC24, WGES24, WGECA24, WGESA24, WGECB24, WGESB24, WGECG24, WGESG24,

WGECR24, WGESR24 are fixed candela units, available in a 75 candela intensity only.  This appliance is ideal for any occupancy that requires notification appliances per the applicable building

or fire code or wherever dependable alarms are required.  
The GEC24, GES24, GEC3-24, GES3-24 strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired (the 15/75Cd model on the GEC24 and GES24 is

additionally listed in compliance with ANSI/UL 1638).  The WGEC24, WGES24, GECA24, GESA24, GECB24,  GESB24, GECG24, GESG24, GECR24, GESR24, WGECA24, WGESA24,

WGECB24, WGESB24, WGECG24, WGESG24, WGECR24, WGESR24 strobe is listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General

Signaling.  Additionally, colored lens models GECA24, GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24 comply with the polar dispersion requirements of ANSI/UL 1971.

II. LOCATION

This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA

documents that provide standards on notification appliances for protective signaling systems.  The GEC24, GES24, GEH24, GEC3-24, GES3-24, GECA24, GESA24, GECB24, GESB24,

GECG24, GESG24, GECR24, GESR24 are intended for indoor installations only; this appliance is 

no

t listed for 

outdoor

or drip proof applications.  The WGEC24, WGES24, WGECA24,

WGESA24, WGECB24, WGESB24, WGECG24, WGESG24, WGECR24, WGESR24 are intended for indoor or outdoor installations; this appliance is rated for outdoor or drip proof applications

when used in conjunction with the GOE or GOELP Enclosure.
Wall mounted strobe and horn/strobe appliances shall have their entire lens at heights above the finished floor of not less than 80 in. (2m) and not greater than 96 in. (2.4m)**.  Spacing shall be

in accordance with Table A.  If a room configuration is not square, the room size that will entirely encompass the room or subdivide the room into multiple squares shall be used.  Wall mounted

horn only appliances shall have their tops above the finished floors at heights of not less than 90 in. (2.30m) and below the finished ceilings at heights of not less than 6 in. (152mm).  Different

mounting heights shall be permitted by the AHJ provided the sound pressure level requirements of NFPA 72 are met.

III. MOUNTING, ROUGH-IN BOX AND RUN WIRING

This unit is designed for mounting to most single gang boxes, 4" square outlet boxes, 2-gang masonry boxes or non-metallic 2-gang switch boxes.  Conduit entrance to boxes should be 

selected to insure sufficient wiring clearance.

1. Run a minimum 18 gauge insulated 2 or more conductor cable.

2. Mount a box for each remote signaling appliance.  Screw bracket onto box. Insert signal into bracket and slide to the right firmly into the terminal block receptacle.  Place housing over 

mounted assembly and screw together with single screw at the bottom of the signal.  Cover screw with plastic tab.

NOTICE:

WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SIGNAL.  INCOMING POSITIVE POWER LEAD MUST BE BROKEN AND EACH LEAD IS

TO BE INSERTED INTO EACH OF THE TOP TWO TERMINALS. IF TWO POWER RUNS ARE MADE TO THE SIGNAL, ONE FOR THE STROBE AND ONE FOR THE HORN, ONLY ONE OF

THE RUNS MUST HAVE ITS POSITIVE LEAD BROKEN AND PLACED UNDER THE TWO SEPARATE TOP TERMINALS. A BARRIER IS PROVIDED TO PREVENT BOTH LEADS FROM

BEING PLACED UNDER THE SAME TERMINAL.

NA = Not allowable

Table A

Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2013 Edition

Maximum Room Size

Minimum Required Light Output ( Effective Intensity, Cd)

Meters

Feet

One Light 

per Room 

Four Lights per Room 

(One Light per Wall)

6.10 x 6.10

20 x 20

15

NA

8.53 x 8.53

28 x 28

30

NA

9.14 x 9.14

30 x 30

34

NA

12.2 x 12.2

40 x 40

60

15

13.7 x 13.7

45 x 45

75

19

15.2 x 15.2

50 x 50

94

30

16.5 x 16.5

54 x 54

110

30

16.8 x 16.8

55 x 55

115

30

18.3 x 18.3

60 x 60

135

30

19.2 x 19.2

63 x 63

150

37

20.7 x 20.7

68 x 68

177

43

21.3 x 21.3

70 x 70

184

60

24.4 x 24.4

80 x 80

240

60

27.4 x 27.4

90 x 90

304

95

30.5 x 30.5

100 x 100

375

95

33.5 x 33.5

110 x 110

455

135

36.6 x 36.6

120 x 120

540

135

39.6 x 39.6

130 x 130

635

185

550-0011

Page 1

GEC24, GES24, GEC3-24, GES3-24 PRODUCT INFORMATION

**Effective Intensity Requirements for Sleeping Areas

Visible Notification Appliance

Distance from Ceiling to Top of Lens  

Intensity

greater than or equal to 24"

110cd

less than 24"

177cd

CAUTION: 

Strobe light must be

installed within 16 feet

of the pillow when

used in a sleeping

area.

ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGES 5 AND 6

Содержание GEC24 Series

Страница 1: ...or outdoor or drip proof applications when used in conjunction with the GOE or GOELP Enclosure Wall mounted strobe and horn strobe appliances shall have their entire lens at heights above the finished...

Страница 2: ...ls Color Lens GECA24 GESA24 Amber GECB24 GESB24 Blue GECG24 GESG24 Green GECR24 GESR24 Red NOTICE DC VOLTAGE RANGE LIMITS 16 33V FWR VOLTAGE RANGE LIMITS 16 33V THIS PRODUCT WAS ONLY TESTED TO THE STA...

Страница 3: ...be lights will NOT be synchronized Place switches 1 and 2 in the ON position on the GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 WGECG24 WGECR24 to power both the audible and visib...

Страница 4: ...STEM CONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility req...

Страница 5: ...ORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SI...

Страница 6: ...MONEY LOSS OF BUSINESS LOSS OF OPPORTUNITY LOSS OF GOODWILL AND LOSS OF REPUTATION THE MAXIMUM LIABILITY OF GENTEX SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE...

Страница 7: ...pos s lorsqu ils sont utilis s avec les bo tiers GOE ou GOELP La lentille au complet des stroboscopes et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur...

Страница 8: ...s e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 164 30 130 196 60 203 325 75 243 355 110 310 491 Mod les Lentille color e GECA24 GESA24 Ambre GECB24 GESB24 Bleu GECG24 GESG24 Vert GECR24...

Страница 9: ...e fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendantes sur les mod les GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 W...

Страница 10: ...NEMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audib...

Страница 11: ...COPE AVIS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMI...

Страница 12: ...N CAS TRE SUP RIEURE AU PRIX D ACHAT DE L APPAREIL VEUILLEZ NOTER QUE CERTAINS TATS PAYS ET PROVINCES N AUTORISENT PAS L EXCLUSION OU LA LIMITATION DES DOMMAGES ACCIDENTELS OU CONS CUTIFS DE SORTE QUE...

Отзывы: