background image

FOR MODELS: GEC3-24, GES3-24, GECA24, GESA24, GECB24, 

GESB24, GECG24, GESG24, GECR24, GESR24 ONLY

To remove bezel, grip both

sides of bezel and pull in a

downward and outward

motion.

FOR MODELS: GEC24, GES24, GEH24, GEC3-24,  GES3-24, GECA24,

GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24 ONLY

V. CHECKOUT AND TROUBLESHOOTING

1. Supply power to the system control panel.  The auxiliary signaling appliances in the system should not be activated.

2. If the signal is activated:

w

Check all smoke and fire detectors in the system to make sure they have not been activated.

w

Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together.  Check wire color codes and traces.

w

Verify that the jumpers and switches are properly set on both the control module and signal appliance.  If the jumper on the AVSM is removed, the horns will not produce any sound unless

there is an input to the H+ and H- terminals on the control module.

3. To test the signal appliances, trip the auxiliary panel or activate the alarm circuit at the main control panel or activate one of the fire detection units in the system.  All auxiliary signals should 

be activated.

4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities 

having jurisdiction.

NOTICE:

THESE TESTING PROCEDURES AND TROUBLESHOOTING INSTRUCTIONS ARE GENERALIZED.  PLEASE REFER TO THE SYSTEM CONTROL PANEL OPERATING

INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM.

SIGNALING APPLIANCE LIMITATION:

Your horn and horn/strobe meet or exceed the current audibility requirements of ANSI/UL 464.  However, if the appliance is located outside a bedroom it may not wake up a sound sleeper,

especially if the room door is closed or only partially open.

VI. TO RETURN AN APPLIANCE

Should you experience problems with your appliance, proceed as follows:

1. Turn off electrical power to the auxiliary alarm circuit.

2. Remove the bezel, nameplate, then mounting screw and slide signal off from bracket

3. Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert.

4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential damage due to shipping or mis-handling).  Include a return address and complete details as to 

the nature of the difficulties being experienced and date of installation.

5. Return to: Gentex Corporation, 10985 Chicago Dr., Zeeland MI 49464.  Prior to returning, call Gentex at 1-800-436-8391 or e-mail [email protected] to obtain a RMA Number from our 

Customer Service Department.

THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER.  AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS, 

GENTEX SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.

Candela selection 

slider switch.  Depress 

center and slide switch to

desired brightness level.

Break off pin and insert into

hole at the bottom of the

selector to lock candela 

setting.  Signal must be

removed from bracket and

pin pushed forward from

backside out of hole to

change candela.

550-0011

Page 4

Содержание GEC24 Series

Страница 1: ...or outdoor or drip proof applications when used in conjunction with the GOE or GOELP Enclosure Wall mounted strobe and horn strobe appliances shall have their entire lens at heights above the finished...

Страница 2: ...ls Color Lens GECA24 GESA24 Amber GECB24 GESB24 Blue GECG24 GESG24 Green GECR24 GESR24 Red NOTICE DC VOLTAGE RANGE LIMITS 16 33V FWR VOLTAGE RANGE LIMITS 16 33V THIS PRODUCT WAS ONLY TESTED TO THE STA...

Страница 3: ...be lights will NOT be synchronized Place switches 1 and 2 in the ON position on the GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 WGECG24 WGECR24 to power both the audible and visib...

Страница 4: ...STEM CONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility req...

Страница 5: ...ORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SI...

Страница 6: ...MONEY LOSS OF BUSINESS LOSS OF OPPORTUNITY LOSS OF GOODWILL AND LOSS OF REPUTATION THE MAXIMUM LIABILITY OF GENTEX SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE...

Страница 7: ...pos s lorsqu ils sont utilis s avec les bo tiers GOE ou GOELP La lentille au complet des stroboscopes et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur...

Страница 8: ...s e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 164 30 130 196 60 203 325 75 243 355 110 310 491 Mod les Lentille color e GECA24 GESA24 Ambre GECB24 GESB24 Bleu GECG24 GESG24 Vert GECR24...

Страница 9: ...e fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendantes sur les mod les GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 W...

Страница 10: ...NEMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audib...

Страница 11: ...COPE AVIS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMI...

Страница 12: ...N CAS TRE SUP RIEURE AU PRIX D ACHAT DE L APPAREIL VEUILLEZ NOTER QUE CERTAINS TATS PAYS ET PROVINCES N AUTORISENT PAS L EXCLUSION OU LA LIMITATION DES DOMMAGES ACCIDENTELS OU CONS CUTIFS DE SORTE QUE...

Отзывы: