24VDC CLEAR Lens Indoor Strobe Current Ratings
GEC24 and
GES24 Series
Available Candela
GEC3-24 and
GES3-24 Series
Available Candela
Strobe
Candela
Regulated 24VDC
Max. Operating
Current(mA)
Regulated 24VFWR
Max. Operating
Current (mA)
1
24VDC
Nominal Operating
Current (mA)
w
15
42
77
30
w
15/75
67
113
N/A
w
30
58
102
42
w
60
97
161
66
w
75
116
225
80
w
110
161
256
103
w
177
213
341
N/A
WGEC24, WGES24, WGECA24, WGESA24, WGECB24, WGESB24, WGECG24, WGESG24, WGECR24, WGESR24 PRODUCT INFORMATION
Models
Color Lens
WGECA24, WGESA24
Amber
WGECB24, WGESB24
Blue
WGECG24, WGESG24
Green
WGECR24, WGESR24
Red
NOTICE:
DC VOLTAGE RANGE LIMITS: 16-33V. FWR
VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS
ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO
NOT APPLY 80% AND 110% OF THIS RANGE FOR
SYSTEM OPERATION.
1 When using products manufactured after 7-1-10, these
values are to be used when calculating current draws.
N/A: 24VDC nominal operating current data not available
NOTICE:
DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY
TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM
OPERATION.
1 When using products manufactured after 7-1-10, these values are to be used when calculating current draws.
24VDC CLEAR & AMBER Lens Outdoor
Strobe Current Ratings
Use with WGEC24, WGES24,
WGECA24, WGESA24 Products
Candela
Regulated 24VDC
Max. Operating
Current (mA)
Regulated 24VFWR
Max. Operating
Current (mA)
1
75
170
263
24VDC BLUE, GREEN & RED Lens Outdoor
Strobe Current Ratings
Use with WGECB24, WGESB24, WGECG24,
WGESG24, WGECR24, WGESR24 Products
Candela
Regulated 24VDC
Max. Operating
Current (mA)
Regulated 24VFWR
Max. Operating
Current (mA)
1
75
164
278
AMBER Lens Indoor Strobe Current Ratings
Use with GECA24 and GESA24 Products
Candela
Regulated 24VDC
Max. Operating
Current (mA)
Regulated 24VFWR
Max. Operating
Current (mA)
1
15
47
82
30
64
112
60
113
178
75
145
213
110
178
259
GECA24, GESA24, GECB24, GESB24, GECG24, GESG24, GECR24, GESR24 PRODUCT INFORMATION
BLUE, GREEN & RED Lens Indoor
Strobe Current Ratings
Use with GECB24, GESB24, GECG24,
GESG24, GECR24, GESR24 Products
Candela
Regulated 24VDC
Max. Operating
Current (mA)
Regulated 24VFWR
Max. Operating
Current (mA)
1
15
105
164
30
130
196
60
203
325
75
243
355
110
310
491
Models
Color Lens
GECA24, GESA24
Amber
GECB24, GESB24
Blue
GECG24, GESG24
Green
GECR24, GESR24
Red
NOTICE
: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS: 16-33V. THIS PRODUCT WAS ONLY TESTED TO THE
STATED VOLTAGE RANGE(S); DO NOT APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.
1
When using products manufactured after 7-1-10, these values are to be used when calculating current draws.
Horn Decibel Levels:
Reverberant Room
Horn Current Ratings Over
Input Voltage Range of 16-33V
24VDC Nominal Horn
Current Ratings
Horn Mode
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(HIGH)
Minimum SPL
at 10Ft. Per
ANSI/UL 464
(LOW)
Regulated 24VDC
Max. Operating
Current (mA)
HIGH Setting
Regulated 24VFWR
Max. Operating
Current (mA)
HIGH Setting
24VDC Operating
Current (mA)
HIGH Setting
24VFWR Operating
Current (mA)
HIGH Setting
Temp 3 2400Hz
78 dBA
71* dBA
28
48
10.7
26.8
Temp 3 Mechanical
76 dBA
70* dBA
25
44
9.7
24.5
Temp 3 Chime
70* dBA
66* dBA
15
30
8.6
20.6
Continuous 2400Hz
81 dBA
74* dBA
28
48
20.4
43.7
Continuous Mechanical
80 dBA
72* dBA
25
44
17.0
39.3
Continuous Chime
70* dBA
66* dBA
15
30
9.6
23.0
Whoop
82 dBA
69* dBA
56
62
45.4
60.2
HORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION
NOTICE:
w
THE THREE PULSE TEMPORAL PATTERN IS TO BE USED FOR EVACUATION USE ONLY.
w
THE SOUND OUTPUT FOR THE TEMPORAL 3 TONE IS RATED LOWER SINCE THE TIME THE HORN IS OFF IS AVERAGED INTO THE SOUND OUT PUT RATING. WHILE THE HORN IS PRODUCING A TONE
IN THE TEMPORAL 3 MODE ITS SOUND PRESSURE IS THE SAME AS THE CONTINUOUS MODE. UNITS HAVE BEEN TESTED TO 0°C, 49°C AND 93% HUMIDITY.
* Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 sound level required for public mode fire protection service.
These settings are acceptable only for private mode fire alarm signaling use. Use the high dBA setting for public mode applications (the chime tone is always private mode).
550-0011
Page 2
Strobe light can not be seen when objects such as doors, furniture or walls block strobe light.
NOTICE:
w
THE VISUAL SIGNAL MUST BE IN THE DIRECT VIEWING AREA OF THE OCCUPANT IN ORDER TO BE SEEN.
w
VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED. VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD
FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.
w
THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE
WILL NOT BE EFFECTIVE.