IV. WIRING

Wiring for synchronized strobes and horns.

Using this method you may:

w

Use only two wires to synchronize the temporal horn and strobe with the ability to mute the horn (place switches 

1

and 

2

in 

the ON position on the GEC24, GEC3-24, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, 

WGECG24, WGECR24).

w

Mute the horn 

only

when the temporal horn option has been selected.

w

Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.

Wiring for synchronized parallel (unison) horn/strobe operation.

Using this method you may:

w

Use four wires where two wires are used to power and synchronize the strobe and two additional wires are used to power 

and synchronize the horn (place switches 

1

and 

2

in the OFF position on the GEC24, GEC3-24, WGEC24, GECA24, 

GECB24, GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24).

w

Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Gentex synchronization protocol. 

w

Use the Gentex synchronization protocol to provide synchronization and mute the horn, if available.  

NOTICE: 

w

FOR THIS OPTION, SWITCHES 

1

AND 

2

ON THE GEC24, GEC3-24, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGEC24, WGECR24 MUST BE IN THE 

OFF POSITION TO ISOLATE POWER TO THE AUDIBLE AND VISIBLE PORTION OF THE CIRCUIT.

w

ALL STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS APPLIED VOLTAGE.  THIS APPLIANCE IS NOT RECOMMENDED FOR USE ON CODED OR PULSING 

SIGNALING CIRCUITS. HOWEVER, USE OF THE AVSM CONTROL MODULE IS  PERMITTED TO SYNCHRONIZE THE STROBE AND/OR MUTE THE HORN.

w

SEE AVSM CONTROL MODULE MANUAL (550-0284, MANUAL ISSUE DATE 2-1-03) FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS.  AVSM MANUAL CAN BE OBTAINED AT 

HTTP://WWW.GENTEX.COM/FIRE/PRODUCTS OR CALL GENTEX CORPORATION AT 1-800-436-8391.

Conventional Method:

You may connect both the strobe and the horn directly from a source of rated power without the use of a control module.  However, the horns and strobe lights will NOT be synchronized.  Place

switches 

1

and 

2

in the ON position on the GEC24, GEC3-24, WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24 to power both the audible and

visible from a single pair of power wires. If you wish to power the horn and strobe from independent sources of power, place switches 

1

and 

2

in the OFF position on the GEC24, GEC3-24,

WGEC24, GECA24, GECB24, GECG24, GECR24, WGECA24, WGECB24, WGECG24, WGECR24 and connect power to the appropriate terminals.

CAUTION:

When using only a single power source to 

energize the strobe and horn (switches 1 and 2 in the ON 

position), the in/out wiring must be under the S+ and S- 

terminals only.  Failure to do so may result in damage to your

signal.  For the horn only (GEH24) and strobe only (GES24,

GES3-24, WGES24, GESA24, GESB24, GESG24, GESR24,

WGESA24, WGESB24, WGESG24, WGESR24), only the top

three terminals are to be used.  

SWITCH POSITION

TONE

3

4

5

Mechanical Temporal 3

ON

ON

ON

Mechanical - Continuous

OFF

ON

ON

2400Hz - Temporal 3

ON

OFF

ON

2400Hz - Continuous

OFF

OFF

ON

Chime - Temporal 3

ON

ON

OFF

Chime - Continuous

OFF

ON

OFF

Whoop

ON

OFF

OFF

Whoop

OFF

OFF

OFF

NOTICE

w

SWITCH POSITIONS 1 AND 2 IN THE OFF POSITION TO 

SELECT ISOLATED HORN AND STROBE POWER INPUTS

w

SWITCH POSITION 6 ON = HIGH DBA

w

SWITCH POSITION 6 OFF = LOW DBA

CAUTION: 

A jumper card is provided to test for correct

wiring in the supervisory mode only.  DO NOT pass alarm

current through the jumper.

Gentex Super-Slide

®

Mounting Bracket:

Allows the installer to pre-wire the system, test for system

supervision, remove the signal head until occupancy,

switch out Gentex signals without changing mounting

brackets and has locking edge connector for snap-in-place

installation.

Gentex Checkmate

®

Instant Voltage Verification:  

It is often necessary to confirm the voltage drop along a

line of devices. The access holes are provided in the back

of the terminal block to allow the voltage to be measured

directly without removing the device. Typically this would

be done at the end of the line to confirm design criteria.

Most measurements will be taken using the S+ and S-

locations although access is provided to other locations. 

NOTICE

: CARE SHOULD BE TAKEN TO NOT SHORT

THE TEST PROBES.

Содержание GEC24 Series

Страница 1: ...or outdoor or drip proof applications when used in conjunction with the GOE or GOELP Enclosure Wall mounted strobe and horn strobe appliances shall have their entire lens at heights above the finished...

Страница 2: ...ls Color Lens GECA24 GESA24 Amber GECB24 GESB24 Blue GECG24 GESG24 Green GECR24 GESR24 Red NOTICE DC VOLTAGE RANGE LIMITS 16 33V FWR VOLTAGE RANGE LIMITS 16 33V THIS PRODUCT WAS ONLY TESTED TO THE STA...

Страница 3: ...be lights will NOT be synchronized Place switches 1 and 2 in the ON position on the GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 WGECG24 WGECR24 to power both the audible and visib...

Страница 4: ...STEM CONTROL PANEL OPERATING INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM SIGNALING APPLIANCE LIMITATION Your horn and horn strobe meet or exceed the current audibility req...

Страница 5: ...ORN DECIBEL AND CURRENT RATINGS PRODUCT INFORMATION HORN HORN STROBE NOTICE w THE NATIONAL BUILDING CODE AND CAN ULC S525 REQUIRES THAT ALL HORNS USED FOR BUILDING EVACUATION PRODUCE TEMPORAL CODED SI...

Страница 6: ...MONEY LOSS OF BUSINESS LOSS OF OPPORTUNITY LOSS OF GOODWILL AND LOSS OF REPUTATION THE MAXIMUM LIABILITY OF GENTEX SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE PLEASE...

Страница 7: ...pos s lorsqu ils sont utilis s avec les bo tiers GOE ou GOELP La lentille au complet des stroboscopes et des avertisseurs ou stroboscopes muraux doit tre plac e au dessus du plancher fini une hauteur...

Страница 8: ...s e maximum de 24 V RDA Courant de fonctionnement mA 1 15 105 164 30 130 196 60 203 325 75 243 355 110 310 491 Mod les Lentille color e GECA24 GESA24 Ambre GECB24 GESB24 Bleu GECG24 GESG24 Vert GECR24...

Страница 9: ...e fils d alimentation Pour alimenter l avertisseur et le stroboscope au moyen de sources d alimentation ind pendantes sur les mod les GEC24 GEC3 24 WGEC24 GECA24 GECB24 GECG24 GECR24 WGECA24 WGECB24 W...

Страница 10: ...NEMENT APPROPRI DU PANNEAU ET DU SYST ME DE D TECTION D INCENDIE LIMITES DE L APPAREIL DE SIGNALISATION L avertisseur et l avertisseur ou stroboscope sont conformes ou surpassent les exigences d audib...

Страница 11: ...COPE AVIS w LE CODE NATIONAL DU B TIMENT ET LA NORME CAN ULC S525 EXIGENT QUE TOUS LES AVERTISSEURS DESTIN S L VACUATION DU B TIMENT DIFFUSENT DES SIGNAUX TEMPORELS CODIFI S w LA PUISSANCE SONORE NOMI...

Страница 12: ...N CAS TRE SUP RIEURE AU PRIX D ACHAT DE L APPAREIL VEUILLEZ NOTER QUE CERTAINS TATS PAYS ET PROVINCES N AUTORISENT PAS L EXCLUSION OU LA LIMITATION DES DOMMAGES ACCIDENTELS OU CONS CUTIFS DE SORTE QUE...

Отзывы: