5. The cable length of the connection between the BACS SPLITTING BOX will reduce the max. length of 6.
6. Total Length of a BACS bus must not exceed 60m/2360in.(4.+ 6.), measured from the BACSWEBMANAGER.
Don‘t connect more than 50 BACS Modules at on BACS bus string.
7. BACS bus cable length between BACS modules for the interconnection, in this example 40cm/16in. Shorter
interconnecting cables would increase the distance of 50m/1970in. accordingly, longer interconnecting cables
would shorten the distance of 50m/1970in.
8. Max. number of BACS Modules is 512.
9. Max. distance from BACS WEBMANAGER to BACS CURRENT SENSORs should not exceed 10m/395in.
10. Max. distance between the BACS_GX_R_AUX and the dry-contacts should not exceed 50m/1970in. in total.
1. Max. cable length 15m/590in. to
COM1/RS232 device (UPS, Gen-
set, Transfer Switch, Charger or
other
battery-powered
device)
managed by BACS.
2. Max. cable length 15m/590in. to
COM2/RS232 for Environmental
sensors
(SM_T_COM,
SM_TH_COM) or 3rd Party Sen-
sors with SENSORMANAGER.
3. Power Supply 12V/2A (UPS pro-
tected). For more than 300 BACS
Modules a 12V/3A Power Supply
is required.
4. Max. cable length from BACS
WEBMANAGER to BACS SPLIT-
TING BOX should not exceed
10m/395in. (Otherwise it will re-
duce the max. length of 6.)
BACS WEBMANAGER BUDGET