Control Electronics
(
continued
)
Alarm & Warn Relay Option Selection
Mode
: The discrete relay options that are
available for the Warn and Alarm relays are:
¤
Energized or De-Energized
¤
Latching or Non-Latching
¤
Set Point
The Alarm & Warn Set Points can be
selected in increments of 5 parts per million
for 0 to 100ppm and 0 to 50ppm ranged
sensors and in increments of 2 parts per
million for 0 to 20ppm ranged sensors.
NOTE: Once the Warn & Alarm Set
Points and Relay Options have been
selected, the unit will revert to the
calibration sequence, and must be
calibrated.
Model S216A
Sensor Assembly
5
Содержание S216A