FL4000
42
FL4000. The master device eventually processes a timeout condition for the query in
order to prevent this condition from occurring; the maximum response time for the
FL4000 is 200 milliseconds. Therefore, the master’s timeout setting should be set to
200 milliseconds or greater.
If the FL4000 receives the query without a communications error, but cannot process it
due to reading or writing to a non-existent FL4000 command register, then the FL4000
returns an exception response message informing the master of the error.
The exception response message has two fields that differentiate it from a normal response.
The first is the function code – byte 2. This code will be 0x83 for a read exception and 0x86 for
a write exception. The second differentiating field is the exception code – byte 3 (Section 4.8.2).
In addition, the total exception response length is 5-bytes rather than the normal message
length.
Table 28: Exception Response
Byte
MODBUS
Range
Referenced to FL4000
1
st
Slave Address
1-247* (Decimal)
FL4000 ID (Address)
2
nd
Function Code
83 or 86 (Hex)
Preset Single Registers
3
rd
Exception Code 01 – 06 (Hex)
Appropriate Exception Code (See Below)
4
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
5
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
* Address 0 is reserved for Broadcast Mode and is not supported at this time.
4.8.2 Exception
Code
Exception Code Field:
In a normal response, the FL4000 returns data and status in the
response data field. In an exception response, the FL4000 returns an exception code
(describing the FL4000 condition) in the data field. Below is a list of exception codes that are
supported by the FL4000:
Table 29: Exception Codes
Code
Name
Description
01
Illegal Function
The function code received in the query is not an allowable
action for the FL4000.
02
Illegal Data Address
The data address received in the query is not an allowable
address for the FL4000.
03
Illegal Data Value
A value contained in the query data field is not an allowable
value for the FL4000.
04
Reserved NA
Содержание FL4000
Страница 2: ...ii FL4000 This page intentionally left blank ...
Страница 8: ...FL4000 viii Figure 2 Mounting Instruction Figure 3 Wall Mounting Assembly ...
Страница 24: ...FL4000 24 Figure 11 Horizontal FOV n Heptane Low Sensitivity Figure 12 Vertical FOV n Heptane High Sensitivity ...
Страница 60: ...FL4000 60 6 2 Final Assembly Figure 26 FL4000 Cross Section View ...