Model FL3112
31
7.7.8 Options
A read returns the status of the settings for the Detector Sensitivity, Relay Delay, Relay
Latching/Non-Latching and Relay Energized/Non-Energized features from EEPROM. A
write command changes the settings for the EEPROM.
Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device
Failure) is returned.
These Functions operate on the Low Data Byte.
Function
Bit Position
Conditions
Access
Warn Energized
8 (MSB)
1 = Energized
Read/Write
0 = Non-Energized
Alarm Energized
7
1 = Energized
Read/Write
0 = Non-Energized
Warn Latched
6
1 = Latched
Read/Write
0 = Non-Latched
Alarm Latched
5
1 = Latched
Read/Write
0 = Non-Latched
(Time Delay in Seconds)
4
8
2 10
Alarm
Time
Delay
2
4
0 0 1 1 Read/Write
Alarm
Time
Delay
1
3
0 1 0 1 Read/Write
(Sensitivity %)
100 75 50
Sensitivity
2 2
0 0 1 Read/Write
Sensitivity 1
1 (LSB)
0
1
0
Read/Write
High Data Byte Not Used
7.7.9 Address
A read returns the address of the FL3112. A write changes the address to the requested
address. The range of the address is 1 to 247 (01 to F7 Hex). After the address has been
changed to the slave unit, the Modbus communications will cease because the address
has changed; therefore the master will have to change its query address to the slave’s new
address in order to restart the communications.
Exception: If an EEPROM write error occurs, then the Exception Code 04 (Slave Device
Failure) is returned.
Содержание FL3112
Страница 15: ...Model FL3112 10 Figure 3 A FL3112 Field of View ...
Страница 16: ...Model FL3112 11 Figure 3 B Outline Drawing ...
Страница 23: ...Model FL3112 18 Figure 3 G Front Cap Assembly ...