Model FL3112
29
7.7 FL3112 Operational Mode Command Register Details
7.7.1 Analogue
A read returns a value, which is proportional to the 0 – 20mA output current. The current is
based on a 16-bit value. The master scaling is 0 – 65535 Decimal which corresponds to
the FL3112 scaling which is 0 – 20mA.
7.7.2 Mode
A read returns the fire status mode of the FL3112.
Mode
Decimal Value
Powerup Delay
1
Warn Non-latching Only
2
Warn & Alarm Non-Latching
3
Warn Latching Only
4
Alarm Latching Only
5
Warn & Alarm Latching
6
Ready State (No Fire)
7
Alarm Test
10
COPM Fault Detected
11
7.7.3 Status/Error
A read returns the errors that are occurring at the present time which are indicated by bit
position.
Byte
Function
Bit Position
Low EEPROM
Checksum
8
EEPROM Checksum
7
RAM Test
6
Low (24V)
Voltage Check
5
Fire Window COPM
4
Fire Sensor COPM
3
Sun COPM
2
Low 12 V
Voltage Check
1
High Not
Used
8-1