Model FL3112
23
7.0 Modbus Serial Communications
7.1 Baud
Rate
The Baud Rate is a selectable setting via the Modbus Communications Interface. The
selectable baud rates are 19200, 9600, 4800 or 2400 bits per second.
7.2 Data
Format
The Data Format is a selectable setting via the Modbus Communications Interface. The
selectable data formats are as follows:
Data Bits Parity Stop
Bit Format
8
None 1
8-N-1
8
Even 1
8-E-1
8
Odd 1
8-O-1
8
None 2
8-N-2
7.3 Modbus
Read
Status
Protocol (Query/Response)
7.3.1 Modbus
Read
Query Message
Byte Modbus Range
Referenced to FL3112
1
st
Slave
1-247* (Decimal) FL3112 ID (Address)
2
nd
Function Code
03
Read Holding Registers
3
rd
Register Address Hi**
00
Not Used by FL3112
4
th
Register Address Lo**
00-FF (Hex)
FL3112 Command Registers
5
th
No. of Registers Hi
00
Not Used by FL3112
6
th
No. of Registers Lo
01
No. of 16 Bit Registers
7
th
CRC Lo
00-FF (Hex)
CRC Lo Byte
8
th
CRC Hi
00-FF (Hex)
CRC Hi Byte
* Note:
Address 0 is reserved for broadcast mode and will not be supported at this time.
** Note: Register Address can be a maximum of 9999 Address Locations (0000-270E)