14
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) seconds of the
engine shutting down.
2. The fuel output will not be energized with the starter.
3. The starter and magneto outputs will be energized together.
4. Once the starter is energized the control board will begin look-
ing for engine rotation. If it does not see an RPM signal within
three (3) seconds it will shut down and latch out on RPM
sensor loss.
5. Once the control board sees an RPM signal it will energize the
fuel solenoid, drive the throttle open and continue the crank
sequence.
6. Starter motor will disengage when speed reaches starter
dropout.
7. If the generator does not reach 2200 RPM within 15 seconds,
re-crank cycle will occur.
8. If engine stops turning between starter dropout and 2200
RPM, the board will go into a rest cycle for seven (7) seconds
then re-crank (if additional crank cycles exist).
9. Once started, the generator will wait for a hold-off period
before starting to monitor oil pressure and oil temperature
(refer to the Alarm Messages section for hold-off times).
10. During Manual start cranking, if the Mode switch is moved
from the Manual position, the cranking stops immediately.
11. During Auto mode cranking, if the remote start contacts OPEN
(OFF), the cranking cycle does NOT abort but continues until
complete. Once the engine starts, it will run for one (1) min-
ute, then shut down.
3.3.4
REMOTE START OFF
Initial Condition: Generator supplying power to customer load.
Once the contacts open, the controller will run the engine through
a one (1) minute cool down period and then shut down.
3.4
SIDE COMPARTMENT
(FIGURES 3.2 & 3.3)
Local codes may require this compartment to be locked. A hasp is
provided so the owner can secure the compartment with their own
padlock. Check local codes in the area.
3.4.1
MAIN CIRCUIT BREAKER
This is a 1-pole breaker rated according to the Specifications sec-
tion.
Figure 3.2 – Side Compartment
Figure 3.3 – Open Side Compartment
3.5 PROTECTION
SYSTEMS
3.5.1 ALARMS
Highest Priority (Latching) Displayed
on the control panel. They
must be cleared before the alarm message goes away. The alarm
log records each occurrence (see Appendix - "Menu System").
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and seven (7) second delay
once the engine is running.
This switch (Figure 3.4) has normally closed contacts that are
held open by engine oil pressure during operation. Should the oil
pressure drop below the five (5) PSI range, switch contacts close
and the engine shuts down. The unit should not be restarted until
oil level is verified.
Operation
Содержание EcoGen 6kW
Страница 27: ...Generac Power Systems Inc 25 25 Drawing No 0J1320 B Installation Diagram...
Страница 28: ...26 Generac Power Systems Inc 26 Installation Diagram Drawing No 0J1320 B...
Страница 29: ...Generac Power Systems Inc 27 27 Drawing No 0J1320 B Installation Diagram...
Страница 31: ...29 Drawing No 0J1323 C Oil Make up System...
Страница 32: ...30 Notes...
Страница 33: ...31 Notes...