1.7  

FUEL REQUIREMENTS AND 
RECOMMENDATIONS

This unit uses a LP vapor withdrawal system only. 

This type of 

system uses the vapors formed above the liquid fuel in the storage 

tank.
Recommended fuels should have a Btu content of at least 2,520 

Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu 

content of the fuel.
Required fuel pressure for 

liquid propane, 10 inches to 12 inches 

of water column (0.36 to 0.43 psi). The primary regulator for the 

propane supply is NOT INCLUDED with the generator.

NOTE:

All pipe sizing, construction and layout must comply NFPA 58 

for liquid propane applications. Once the generator is installed, 

verify that the fuel pressure NEVER drops below 10 inches 

water column.

Prior to installation of the generator, the installer should consult 

local fuel suppliers or the fire marshal to check codes and regula-

tions for proper installation. Local codes will mandate correct rout-

ing of gaseous fuel line piping around gardens, shrubs and other 

landscaping to prevent any damage.
Special considerations should be given when installing the unit 

where local conditions include flooding, tornados, hurricanes, 

earthquakes and unstable ground for the flexibility and strength of 

piping and their connections.
Use an approved pipe sealant or joint compound on all threaded 

fitting.
All installed gaseous fuel piping must be purged and leak tested 

prior to initial start-up in accordance with local codes, standards 

and regulations.

1.8 FUEL 

CONSUMPTION

Unit

LP Vapor

1/2 Load

Full Load

6 kW

0.82/30

1.47/54

** LP is in gallons per hour/cubic feet per hour.

*** Values given are approximate.

Verify that gas pipe and regulator is capable of providing enough 

fuel flow to include household appliances.

 

Gaseous fuels such as liquid propane (LP) 

gas are highly explosive. Even the slightest 

spark can ignite fuel and cause an explo-

sion. No leakage of fuel is permitted. LP gas 

is heavier than air and tends to settle in low 

areas.

NOTE:

A minimum of one approved manual shut-off valve must be 

installed in the gaseous fuel supply line. The valve must be eas-

ily accessible. Local codes determine the proper location.

1.9 LOCATION

n

 

The engine exhaust fumes contain carbon 

monoxide, which can be DEADLY. This dan-

gerous gas, if breathed in sufficient con-

centrations, can cause unconsciousness or 

even death. This generator must be installed 

properly, in strict compliance with applicable 

codes and standards. Following installation, 

do nothing that might render the system 

unsafe or in noncompliance with such codes 

and standards.

Operate the generator outdoors ONLY.

•   Keep exhaust gases from entering a confined 

area through windows, doors, ventilation, crawl 

spaces or other openings (Figure 1.3).

•   It is highly recommended that carbon monox-

ide detector(s) be installed indoors according 

to the manufacturer's instructions/recommen-

dations.

•   The generator must me mounted safely per 

applicable codes and the manufacturer's speci-

fications. Do NOT alter or add to the exhaust 

system, or do anything that might render the 

exhaust system unsafe or in noncompliance 

with applicable codes and standards.

1.9.1 GENERATOR

Install the generator set, in its protective enclosure, 

outdoors

where adequate cooling and ventilating air is always available 

(Figure 1.3). Consider these factors:

The installation of the generator 

• 

must comply strictly with 

NFPA 37, NFPA 58, and NFPA 70 standards.

Install the unit where air inlet and outlet openings will not 

• 

become obstructed by leaves, grass, snow, etc.. If prevailing 

winds will cause blowing or drifting, consider using a wind-

break to protect the unit.

Install the generator on high ground where water levels will not 

• 

rise and endanger it.

Allow sufficient room on all sides of the generator for mainte-

• 

nance and servicing. This unit must be installed in accordance 

with current applicable NFPA 37 and NFPA 70 standards; as 

well as any other federal, state and local codes for minimum 

distances from other structures. DO NOT install under wooden 

decks or structures unless there is at least four (4) feet of clear-

ance above the generator, three (3) feet of clearance on sides 

and front, and 18 inches of clearance at back of unit.

Install the unit where rain gutter down spouts, roof run-off, 

• 

landscape irrigation, water sprinklers or sump pump discharge 

does not flood the unit or spray the enclosure, including any air 

inlet or outlet openings.

 6 

General Information

Содержание EcoGen 6kW

Страница 1: ...enerator Owner s Manual LISTED C US NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DEADLY EXHAUST FUMES OUTDOOR INSTA...

Страница 2: ...3 Electrical Checks 10 2 4 Generator Tests Under Load 12 2 5 Checking Automatic Operation 12 Operation 12 3 1 Control Panel Interface 12 3 2 Automatic Operation 13 3 3 Sequence of Automatic Operation...

Страница 3: ...mation each indicates is as follows nThis symbol points out important safety information that if not followed could endanger personal safety and or property of others This symbol points out potential...

Страница 4: ...to correct generator operation Do not alter the instal lation or permit even partial blockage of ventilation provisions as this can seriously affect safe operation of the generator The generator MUST...

Страница 5: ...e Consult the local fire department with any ques tions pertaining to fire extinguishers EXPLOSION HAZARDS Do not smoke around the generator Wipe up any fuel or oil spills immediately Ensure that no c...

Страница 6: ...tions For that reason the engine is equipped with the fol lowing systems that protect it against potentially damaging condi tions 1 Low Oil Pressure Sensor 6 Low Battery 2 High Temperature Sensor 7 Un...

Страница 7: ...rs 1 5 2 ENGINE Type of Engine GT 530 Number of Cylinders 2 Rated Horsepower 3 600 rpm 18 Displacement 530cc Cylinder Block Aluminum w Cast Iron Sleeve Valve Arrangement Overhead Valves Ignition Syste...

Страница 8: ...es determine the proper location 1 9 LOCATION nThe engine exhaust fumes contain carbon monoxide which can be DEADLY This dan gerous gas if breathed in sufficient con centrations can cause unconsciousn...

Страница 9: ...the enclosure Annex A Explanatory Material A4 1 4 2 Means of demonstrating compliance are by means of full scale fire test or by calculation procedures Because of the limited spaces that are frequentl...

Страница 10: ...of vegetation Clearance at the top should be a minimum of 48 inches from any structure overhang or projections from the wall The generator should not be placed under a deck or other structure that is...

Страница 11: ...erator con trol panel Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of the battery Disconnect chargin...

Страница 12: ...INITIAL START UP NOTE These units have been run and tested at the factory prior to being shipped and do not require any type of break in NOTE This unit comes filled with oil from the factory Check the...

Страница 13: ...Use ARROW keys to scroll and find the first number of your Activation Code Press ENTER to select Repeat this step until all digits have been entered Use ESCAPE to correct previous digits Display Read...

Страница 14: ...vidence of overheat ing etc 9 When testing under load is complete turn OFF electrical loads 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Let the engine run at no load for...

Страница 15: ...menu is reached This page displays the following options HISTORY STATUS EDIT AND DEBUG See the Appendix Menu System 3 2 AUTOMATIC OPERATION To select automatic operation do the following 1 Make sure t...

Страница 16: ...stops immediately 11 During Auto mode cranking if the remote start contacts OPEN OFF the cranking cycle does NOT abort but continues until complete Once the engine starts it will run for one 1 min ute...

Страница 17: ...shut down The under frequency setting is 55 Hz Internal Fault Shutdown Alarm This alarm cannot be cleared call service dealer Undervoltage Shutdown Alarm If the generator voltage falls below 85 of no...

Страница 18: ...ILL ABOVE THE FULL MARK 5 Install the dipstick 6 Reset the AUTO OFF MANUAL switch to its original position 7 If the generator was running first turn the generator s main circuit breaker back to the ON...

Страница 19: ...AUTO position 8 Dispose of used oil at a proper collection center Repeat steps 2 and 3 for the oil reservoir 4 4 CHANGING THE ENGINE AIR CLEANER See The Generator section for the location of the air c...

Страница 20: ...be followed DO NOT SMOKE when near the battery DO NOT cause flame or spark in battery area Discharge static electricity from body before touching the battery by first touching a ground ed metal surfa...

Страница 21: ...er have a Dealer thoroughly clean dry and inspect the generator If the structure ex home has been flooded it should be inspected by a certified electrician to ensure there won t be any electrical prob...

Страница 22: ...erator control panel Start the unit by moving the AUTO OFF MANUAL switch to MANUAL Allow the unit to warm up thoroughly 8 Stop the unit by setting the AUTO OFF MANUAL switch to OFF 9 Turn on the utili...

Страница 23: ...2Y or 500 hours of operation COOLING Enclosure louvers X X W BATTERY Remove corrosion ensure dryness X X M Clean and tighten battery terminals X X M Check charge state X R EVERY 6 M Electrolyte level...

Страница 24: ...k plug s 2 Clean re gap or replace plug s 3 Fuel pressure incorrect 3 Confirm fuel pressure to regulator is 10 12 water column 0 36 0 43 psi for LP 4 Choke remains closed 4 Verify choke solenoid moves...

Страница 25: ...e same navigation method to select the the desired screen refer to the Menu System diagram 6 1 1 CHANGING SETTINGS EDIT MENU To change a setting such as display contrast go to the EDIT menu and use th...

Страница 26: ...E DEBUG INPUTS OUTPUTS DISPLAYS EDIT CONTRAST LANGUAGE TIME DATE EXERCISE TIME SPEED ESC Press the ESCAPE key to jump back up through the menu levels Use the key to navigate through the menu ENTER Use...

Страница 27: ...Generac Power Systems Inc 25 25 Drawing No 0J1320 B Installation Diagram...

Страница 28: ...26 Generac Power Systems Inc 26 Installation Diagram Drawing No 0J1320 B...

Страница 29: ...Generac Power Systems Inc 27 27 Drawing No 0J1320 B Installation Diagram...

Страница 30: ...T BATTERY VOLTAGE SENSING AC DISTRIBUTION PANEL 120 240V DC DISTRIBUTION PANEL 12V 24V 48V BATTERY 12V 24V 48V INVERTER CHARGER GENERATOR HOUSE HOUSE LOADS HOUSE LOADS 120V 240V CHARGER SUPPLY TWO WIR...

Страница 31: ...29 Drawing No 0J1323 C Oil Make up System...

Страница 32: ...30 Notes...

Страница 33: ...31 Notes...

Страница 34: ...ponsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs The warranty repairs should be completed in a reasonable amount of time not to exceed 30 days Warranty service...

Страница 35: ...hat part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by Generac according to Subsection 4 below Any such emissions related part repaired or replac...

Страница 36: ...er service does not normally exist without a renewable energy system including an inverter battery bank and alternative energy power source Fuel connections other than conventional utility company sup...

Отзывы: