4.3.3 

OIL & OIL FILTER CHANGE PROCEDURE

To change the oil, proceed as follows:
1.  Start the engine by moving the AUTO/OFF/MANUAL switch to 

MANUAL and run until it is thoroughly warmed up. Then shut 

OFF the engine by moving the switch to the OFF position.

2.  Immediately after the engine shuts OFF, pull the oil drain hose 

(Figure 4.1) free of its retaining clip. Remove the cap from the 

hose and drain the oil into a suitable container.

3.  After the oil has drained, replace the cap onto the end of the 

oil drain hose. Retain the hose in the clip.

Change the engine oil filter as follows:
1.  With the oil drained, remove the old oil filter by turning it 

counterclockwise.

2.  Apply a light coating of clean engine oil to the gasket of the 

new filter. See the Specifications section for recommended 

filter.

3.  Screw the new filter on by hand until its gasket lightly contacts 

the oil filter adapter. Then, tighten the filter an additional 3/4 to 

one turn (Figure 3.4).

4.  Refill with the proper recommended oil (see the Engine Oil 

Recommendations section). See the Specifications section 

for oil capacities.

5.  Start the engine, run for one (1) minute, and check for leaks.
6.  Shutdown and recheck oil level, add as needed. DO NOT 

OVER FILL.

7.  Reset the AUTO/OFF/MANUAL switch to the AUTO position.
8.  Dispose of used oil at a proper collection center.
* Repeat steps 2 and 3 for the oil reservoir.

4.4  

CHANGING THE ENGINE AIR 
CLEANER

See "The Generator" section for the location of the air cleaner. Use 

the following procedures (Figure 4.2):
1.  Lift the roof and remove the door.
2.  Turn the two screws 1/4 turn counterclockwise to loosen.
3.  Remove the cover and air filter.
4.  Wipe away dust or debris from inside of the air box and 

around edges.

5.  Install the new air cleaner into the air box.
6.  Install the cover. Turn the two cover screws 1/4 turn clock-

wise to tighten.

See the Service Schedule section for air cleaner maintenance. See 

the Specifications section for air filter replacement part number.

Figure 4.2 — Engine Air Cleaner

4.5 SPARK 

PLUGS

Reset the spark plugs gap or replace the spark plugs as necessary. 

See the Service Schedule section for maintenance requirements.
1.  Clean the area around the base of the spark plugs to keep dirt 

and debris out of the engine. 

2.  Remove the spark plugs and check the condition. Replace 

the spark plugs if worn or if reuse is questionable. See the 

Service Schedule section for recommended inspection. Clean 

by scraping or washing using a wire brush and commercial 

solvent. Do not blast the spark plugs to clean.

3.  Check the spark plug gap using a wire feeler gauge. Adjust the 

gap to 0.76 mm (0.030 inch) by carefully bending the ground 

electrode (Figure 4.3).

Figure 4.3 – Setting the Spark Plug Gap

Maintenance

Содержание EcoGen 6kW

Страница 1: ...enerator Owner s Manual LISTED C US NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DEADLY EXHAUST FUMES OUTDOOR INSTA...

Страница 2: ...3 Electrical Checks 10 2 4 Generator Tests Under Load 12 2 5 Checking Automatic Operation 12 Operation 12 3 1 Control Panel Interface 12 3 2 Automatic Operation 13 3 3 Sequence of Automatic Operation...

Страница 3: ...mation each indicates is as follows nThis symbol points out important safety information that if not followed could endanger personal safety and or property of others This symbol points out potential...

Страница 4: ...to correct generator operation Do not alter the instal lation or permit even partial blockage of ventilation provisions as this can seriously affect safe operation of the generator The generator MUST...

Страница 5: ...e Consult the local fire department with any ques tions pertaining to fire extinguishers EXPLOSION HAZARDS Do not smoke around the generator Wipe up any fuel or oil spills immediately Ensure that no c...

Страница 6: ...tions For that reason the engine is equipped with the fol lowing systems that protect it against potentially damaging condi tions 1 Low Oil Pressure Sensor 6 Low Battery 2 High Temperature Sensor 7 Un...

Страница 7: ...rs 1 5 2 ENGINE Type of Engine GT 530 Number of Cylinders 2 Rated Horsepower 3 600 rpm 18 Displacement 530cc Cylinder Block Aluminum w Cast Iron Sleeve Valve Arrangement Overhead Valves Ignition Syste...

Страница 8: ...es determine the proper location 1 9 LOCATION nThe engine exhaust fumes contain carbon monoxide which can be DEADLY This dan gerous gas if breathed in sufficient con centrations can cause unconsciousn...

Страница 9: ...the enclosure Annex A Explanatory Material A4 1 4 2 Means of demonstrating compliance are by means of full scale fire test or by calculation procedures Because of the limited spaces that are frequentl...

Страница 10: ...of vegetation Clearance at the top should be a minimum of 48 inches from any structure overhang or projections from the wall The generator should not be placed under a deck or other structure that is...

Страница 11: ...erator con trol panel Remove watches rings or other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of the battery Disconnect chargin...

Страница 12: ...INITIAL START UP NOTE These units have been run and tested at the factory prior to being shipped and do not require any type of break in NOTE This unit comes filled with oil from the factory Check the...

Страница 13: ...Use ARROW keys to scroll and find the first number of your Activation Code Press ENTER to select Repeat this step until all digits have been entered Use ESCAPE to correct previous digits Display Read...

Страница 14: ...vidence of overheat ing etc 9 When testing under load is complete turn OFF electrical loads 10 Set the generator s main circuit breaker to its OFF or OPEN position 11 Let the engine run at no load for...

Страница 15: ...menu is reached This page displays the following options HISTORY STATUS EDIT AND DEBUG See the Appendix Menu System 3 2 AUTOMATIC OPERATION To select automatic operation do the following 1 Make sure t...

Страница 16: ...stops immediately 11 During Auto mode cranking if the remote start contacts OPEN OFF the cranking cycle does NOT abort but continues until complete Once the engine starts it will run for one 1 min ute...

Страница 17: ...shut down The under frequency setting is 55 Hz Internal Fault Shutdown Alarm This alarm cannot be cleared call service dealer Undervoltage Shutdown Alarm If the generator voltage falls below 85 of no...

Страница 18: ...ILL ABOVE THE FULL MARK 5 Install the dipstick 6 Reset the AUTO OFF MANUAL switch to its original position 7 If the generator was running first turn the generator s main circuit breaker back to the ON...

Страница 19: ...AUTO position 8 Dispose of used oil at a proper collection center Repeat steps 2 and 3 for the oil reservoir 4 4 CHANGING THE ENGINE AIR CLEANER See The Generator section for the location of the air c...

Страница 20: ...be followed DO NOT SMOKE when near the battery DO NOT cause flame or spark in battery area Discharge static electricity from body before touching the battery by first touching a ground ed metal surfa...

Страница 21: ...er have a Dealer thoroughly clean dry and inspect the generator If the structure ex home has been flooded it should be inspected by a certified electrician to ensure there won t be any electrical prob...

Страница 22: ...erator control panel Start the unit by moving the AUTO OFF MANUAL switch to MANUAL Allow the unit to warm up thoroughly 8 Stop the unit by setting the AUTO OFF MANUAL switch to OFF 9 Turn on the utili...

Страница 23: ...2Y or 500 hours of operation COOLING Enclosure louvers X X W BATTERY Remove corrosion ensure dryness X X M Clean and tighten battery terminals X X M Check charge state X R EVERY 6 M Electrolyte level...

Страница 24: ...k plug s 2 Clean re gap or replace plug s 3 Fuel pressure incorrect 3 Confirm fuel pressure to regulator is 10 12 water column 0 36 0 43 psi for LP 4 Choke remains closed 4 Verify choke solenoid moves...

Страница 25: ...e same navigation method to select the the desired screen refer to the Menu System diagram 6 1 1 CHANGING SETTINGS EDIT MENU To change a setting such as display contrast go to the EDIT menu and use th...

Страница 26: ...E DEBUG INPUTS OUTPUTS DISPLAYS EDIT CONTRAST LANGUAGE TIME DATE EXERCISE TIME SPEED ESC Press the ESCAPE key to jump back up through the menu levels Use the key to navigate through the menu ENTER Use...

Страница 27: ...Generac Power Systems Inc 25 25 Drawing No 0J1320 B Installation Diagram...

Страница 28: ...26 Generac Power Systems Inc 26 Installation Diagram Drawing No 0J1320 B...

Страница 29: ...Generac Power Systems Inc 27 27 Drawing No 0J1320 B Installation Diagram...

Страница 30: ...T BATTERY VOLTAGE SENSING AC DISTRIBUTION PANEL 120 240V DC DISTRIBUTION PANEL 12V 24V 48V BATTERY 12V 24V 48V INVERTER CHARGER GENERATOR HOUSE HOUSE LOADS HOUSE LOADS 120V 240V CHARGER SUPPLY TWO WIR...

Страница 31: ...29 Drawing No 0J1323 C Oil Make up System...

Страница 32: ...30 Notes...

Страница 33: ...31 Notes...

Страница 34: ...ponsible for contacting a Generac Authorized Warranty Dealer as soon as a problem occurs The warranty repairs should be completed in a reasonable amount of time not to exceed 30 days Warranty service...

Страница 35: ...hat part If the part fails prior to the first scheduled replacement the part shall be repaired or replaced by Generac according to Subsection 4 below Any such emissions related part repaired or replac...

Страница 36: ...er service does not normally exist without a renewable energy system including an inverter battery bank and alternative energy power source Fuel connections other than conventional utility company sup...

Отзывы: