18
4.1 FUSE
The 7.5 amp fuse on the control panel protects the DC control cir-
cuit against overload (Figure 3.1). This fuse is wired in series with
the battery output lead to the panel. If this fuse element has melted
open, the engine will not be able to crank or start. Replace this fuse
using only an identical 7.5 amp replacement fuse. Whenever the
fuse is removed or replaced, the exercise timer needs to be reset.
4.2
CHECKING THE ENGINE OIL
LEVEL
For oil capacities, see the Specifications section. For engine oil
recommendations, see the Engine Oil Recommendations section.
When power outages necessitate running the generator for extend-
ed periods of time, the oil level should be checked daily.
To check the engine oil level, proceed as follows (Figures 4.1 and
4.2):
1. If the generator is running during a utility outage, first turn OFF
all associated loads running in the residence. Second, turn the
generator's main circuit breaker to the OFF position.
2. Move the AUTO/OFF/MANUAL switch to the OFF position.
3. Remove the dipstick and wipe it dry with a clean cloth.
4. Completely insert the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If necessary, add
oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL”
MARK.
5. Install the dipstick.
6. Reset the AUTO/OFF/MANUAL switch to its original position.
7. If the generator was running during a utility outage, first turn
the generator's main circuit breaker back to the ON position.
Second, turn ON needed loads in the residence.
Figure 4.1 — Oil Dipstick, 8 KVA
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
Figure 4.2 — Oil Dipstick and Fill, 10 & 13 KVA
4.3 CHANGING THE ENGINE OIL
Hot oil may cause burns. Allow engine to
cool before draining oil. Avoid prolonged
or repeated skin exposure with used oil.
Thoroughly wash exposed areas with soap.
4.3.1 OIL
CHANGE
INTERVALS
See the "Service Schedule" section.
4.3.2
ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum Institute (API)
Service Class SJ, SL or better. Use no special additives. Select the
appropriate viscosity oil grade according to the expected operating
temperature.
• SAE 30
Above 32° F
• 10W-30
Between 40° F and -10° F
• Synthetic 5W-30
10° F and below
S A E 3 0
S A E 3 0
S y n t h e t i c 5 W - 3 0
S y n t h e t i c 5 W - 3 0
1 0 W - 3 0
1 0 W - 3 0
Maintenance
Содержание 0j2083
Страница 30: ...28 Installation Diagrams Drawing No 0J3244 B ...
Страница 31: ...29 Drawing No 0J3244 B Installation Diagrams ...
Страница 32: ...Part No 0J2083 Revision G 04 02 13 Printed in U S A ...
Страница 61: ...59 59 Notas ...
Страница 62: ...Nº de parte 0J2083 Revisión G 02 04 13 Impreso en EE UU ...
Страница 90: ...88 ДЛЯ ЗАМЕТОК ...
Страница 91: ...89 89 ДЛЯ ЗАМЕТОК ...
Страница 92: ... элемента 0J2083 Редакция G 04 02 13 Напечатано в США ...