21
The requirements for Site Initiated Auto
Downloading are as follows:
1. Download Computer running PCPreset.
2. Program the telephone number of the
Download Computer in location [90]
Callback Telephone Number.
3. Program location [93] with the number of
the PCPreset account that is to be
downloaded.
PCPreset
1. Create the GEM-P801 account to be
downloaded using PCD-Windows
Quickloader Software.
1. Create a List using PCPreset.
2. Select the account by pressing
t
.
Select the desired account from the list of
PCD3000 accounts available. (The
location in the list is the
Auto Download
ID Number
[93])
3. Tag the list by entering
aD
(
download)
4. Enter Standby Mode by entering
o
.
The Computer is now in STANDBY
Site
At the site perform the following three steps:
1. Arm the panel.
2. Disarm the panel.
3. Enter
A6
. The panel will now
call the download computer running
PCPreset. PCPreset will answer the call,
establish a connection, and then
download the account that matches the
Auto Download ID Number
[93] with the
account of the same number in the list
that PCPreset is currently running.
Dealer Programming
[94]Dealer Code
The default Dealer Code is
4567
. Program
a new 4-digit Dealer Code. When the panel
is defaulted the Dealer Code will be
changed back to the default Dealer Code of
4567
only
if Dealer Code Lockout [96-1]
has not
been programmed.
[95]User 1 Code
The 1st User code is a program code as
well as an Arm/Disarm code. The default
User Code is
1234
. If User 1 Code
Lockout is programmed the User 1 Code
cannot be programmed from User Program
Mode.
[96]Dealer Options 1
(1) Dealer Code Lockout
- Program to
prevent the Dealer Code from changing
with a panel default.
(2) User 1 Code Lockout
- If programmed
the User 1 Code cannot be programmed
from User Program Mode.
(3) Household Fire
- Activates the
following UL required features:
There is a 4 hour re-sound of wireless
Smoke Low Battery and wireless Smoke
Supervisory system troubles.
•
An active System Battery test performed
every 4 hours instead of 24 hours and
Wireless Smoke Supervisory Timer is set
to 4 hours.
•
Fire Bell Timing is March Time.
•
Wireless Smoke Supervisory Time is
fixed at 4 hours.
(4) Fire Trouble on Fire LED
- Normally all
troubles are displayed on the
H
SYSTEM
TROUBLE LED, including Fire Trouble. If
required Fire Trouble can be displayed on the
Fire LED. Fire Trouble is indicated by a
steady
I
Fire LED.
[97]Dealer Options 2
(1) International Dialing Protocol
- No
dialing if no dial tone, 60 s between attempts
and 4 s wait for dial tone.
(2) Invert Bell Output
- Inverts the Bell
polarity and removes supervision from the
bell circuit.
(3) System Trouble Auto Restore
-
Normally, System troubles require
acknowledgment (View System Trouble) in
order to restore. If this option is selected
troubles will restore without requiring
acknowledgment.
(4) User 1 Code-Program only
- If enabled
User 1 Code will function only as the User
Program Code and will not Arm/Disarm the
panel.