MagicControl 4.0 (CM40)
After filter pressure monitoring
•
105
Measurement configuration
•
Volume flow duct
•
Tube type =
Round
•
Tube diameter (duct diameter) must be configured
– The tube diameter is shown in the assembly drawing of the
ducting.
An incorrect diameter leads to an incorrect air volume result!
•
Measurement methods:
– Single
– Selective
–
Time
We recommend the “Temporal” variant. With this variant, the
exhaust air volume is measured over a defined time period. A
measuring time of 60 seconds produces a precise result.
•
Measurement direction =
Exhaust air