Rev. 01 12/21
MagicControl 4.0 (CM40)
After filter pressure monitoring
•
101
OptiControl ISC09 Adjustment instructions
Introduction
The rated air volume flow is automatically controlled by the fan operating
point Δp.
The 3 values of the
System pressur
e Δp
must be determined and
entered beforehand (see below: "Calibration when operating with
frequency converter").
The motor frequency can now be set to the operating point, which
generates the corresponding volume flow.
When the
Fan Δp
increases, due to an increasing filter resistance, the
frequency is corrected and the operating point is adjusted.
When replacing the filter cartridges, the
Fan Δp
decreases. In this case,
the frequency is corrected and the operating point is shifted downwards.
Calibration when operating with frequency
converter
1.
Set the speed (frequency) to 50 Hz
2.
Adjust the throttle valve on the after filter so that the Fan Δp displays
the pressure value
3
“ATEX: Stop powder”
.
3.
Measure the actual air volume in the ducting with an anemometer.
– If the air volume is correct, continue with step 4.
– If the measured air volume flow does not correspond to the set
value, the flap position on the after filter must be changed until
the volume flow measured with the anemometer corresponds to
the set value. (in this example 9,600 m³/h)
4.
Enter the actual value of the
Δp ATEX: Stop powder
manually
under
6
.
Содержание CM40
Страница 28: ...Rev 01 12 21 28 Product description MagicControl 4 0 CM40 ...
Страница 64: ...Rev 01 12 21 64 Operation MagicControl 4 0 CM40 ...
Страница 82: ...Rev 01 12 21 82 Maintenance Repairs MagicControl 4 0 CM40 ...
Страница 92: ...Rev 01 12 21 92 Diagnostic MagicControl 4 0 CM40 ...
Страница 120: ...Rev 01 ...