SM32 • Instruction manual
83
Espaňol
Deutsc
he
Fr
ançais
Eng
lish
Italiano
Terminals
Function
Voltage, Current
37
Power supply of the ML and MLP signals
(35V max)
52
(Common) Ground of the precharge enable control
-
70, 72
OK Relay
(max 250V, 1A – AC11)
81, 82
Blown fuse. On SM32-480-1050, 1500 and 2000A sizes only.
Figura 2.4.1: Localización de los bornes
Tamaños 185 ... 650 A
Tamaños 1050 ... 1500 A
A) = bornes de control, B) = bornes de potencia
C = bornes de potencia (U3, V3) y bornes de control (81, 82)
2.5. Protecciones
2.5.1.
Componentes de protección internos
Converter
Designation
Varistors
SM32-480-185...2000
V1, V2, V3
575 V / 220 J Ø 20 mm
2.5.2. Fusibles internos
Converter
Designation
Fuses
SM32-480-185
F11, F21, F31
16A, 500V
fast, 6 x 32 mm
SM32-480-280
SM32-480-420
SM32-480-650
SM32-480-1050
25A, 500V
fast, 6 x 32 mm
SM32-480-1500
SM32-480-2000
Converter
Designation
Fuses for
Fuses
SM32-480-185
F 4
Power supply
protection
4A, 500V
f a s t
6 x 32 mm
SM32-480-280
SM32-480-420
SM32-480-650
F 5
+24V
protection
1A, 250V
slow
5 x 20 mm
SM32-480-1050
SM32-480-1500
SM32-480-2000
Converter
Designation
Fuses for
Fuses
SM32-480-1500
F10
Cooling fan
protection
6.3 x 32mm,
500V, 1.6A slow
SM32-480-2000