32
SM32 • Instruction manual
Espaňol
Deutsc
he
Fr
ançais
Eng
lish
Italiano
•
mains power supply voltage 3 x 380V (conservative value if referred to a
rated voltage of 3 x 400V)
•
there are two value columns referring to a continuous functioning (class 1) or
to a functioning during an overload phase (class 2) (150% for 60 seconds).
Rated motor
power
Motor
efficiency
Current
DC-Link I
dcl
Fuses DC-Link
superfast
ADV200-… Sizes
P
mot
[kW]
η
mot
Continuous class 1 [A]
Overload class 2 [A]
[A]
Class 1
Class 2
0.55
0.71
1.56
2.34
6
1007
1007
0.75
0.74
2.04
3.06
6
1007
1007
1.1
0.75
2.95
4.42
6
1007
1015
1.5
0.75
4.02
6.03
8
1007
1015
2.2
0.79
5.60
8.39
10
1015
1022
3
0.81
7.44
11.16
16
1022
1030
4
0.83
9.68
14.53
16
1030
1040
5.5
0.84
13.16
19.74
20
1040
2055
7.5
0.86
17.53
26.29
30
2055
2075
11
0.88
25.12
37.68
40
2075
2110
15
0.89
33.87
50.80
63
2110
3150
18.5
0.905
41.08
61.62
63
3150
3185
22
0.912
48.48
72.72
80
3185
3220
30
0.918
65.67
98.51
100
3220
4300
37
0.923
80.56
120.84
125
4300
4370
45
0.93
97.24
145.86
160
4370
4450
55
0.935
118.21
177.32
200
4450
5550
75
0.943
159.83
239.75
250
5550
5750
90
0.946
191.19
286.78
315
5750
5900
110
0.947
233.43
350.14
350
5900
61100
132
0.951
278.94
418.40
450
61100
61320
160
0.955
336.69
505.03
500
61320
71600
200
0.958
419.54
629.31
630
71600
72000
250
0.96
523.33
785.00
800
72000
72500
315
0.963
657.35
986.02
1000
72500
73150
355
0.963
740.82
1111.23
73150
73550
400
0.965
833.00
1249.50
73550
(*) The DC-Link fuses are not included in the converter
The current value in column Current DC-Link
I
dcl
Continuous class 1“ is calcu
-
lated as:
I
dcl
= P
mot
/ (η
mot
* η
l
* U
ln
* 1.35)
where for column ‘‘Current DC-Link I
dcl
Overload class 2“ it is obtained multiply
-
ing by 1.36.
2.7 Markings
CE (Directives LVD 2014/35/EU, EMC 2014/30/EU).