Italiano
Terminals
Function
Voltage, Current
52
(Common) Ground of the precharge enable control
-
70, 72
OK Relay
(max 250V, 1A – AC11)
81, 82
Blown fuse. On SM32-480-1050, 1500 and 2000A sizes only.
Figura 2.4.1: Localisation des bornes
Taille 185 ... 650 A
Taille 1050 ... 1500 A
A) = bornes de contrôle, B) = bornes de puissance
C) = bornes de puissance (U3, V3) et bornes de contrôle (81, 82)
2.5. Protections
2.5.1. Composants internes de protection
Converter
Designation
Varistors
SM32-480-185...2000
V1, V2, V3
575 V / 220 J Ø 20 mm
2.5.2. Fusibles intérieurs
Converter
Designation
Fuses
SM32-480-185
F11, F21, F31
16A, 500V
fast, 6 x 32 mm
SM32-480-280
SM32-480-420
SM32-480-650
SM32-480-1050
25A, 500V
fast, 6 x 32 mm
SM32-480-1500
SM32-480-2000
Converter
Designation
Fuses for
Fuses
SM32-480-185
F 4
Power supply
protection
4A, 500V
f a s t
6 x 32 mm
SM32-480-280
SM32-480-420
SM32-480-650
F 5
+24V
protection
1A, 250V
slow
5 x 20 mm
SM32-480-1050
SM32-480-1500
SM32-480-2000
Converter
Designation
Fuses for
Fuses
SM32-480-1500
F10
Cooling fan
protection
6.3 x 32mm,
500V, 1.6A slow
SM32-480-2000