9 Plc7 fault
4
0 Plc8 fault
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.39
4720 Alm autoreset time
s
FLOAT
0.0
0.0
60.0
ERW
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the AFE product is set to restart.
If some alarms are still enabled the AFE product is set to execute a new attempt at
automatic reset.
At each attempted reset a counter increases. If the limit set in the
PAR 4722 Alm
autoreset number
parameter is reached the AFE product is set to make no more at
-
tempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no
alarms are enabled.
If the parameter is 0 the function is disabled.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
15.40
4722 Alm autoreset number
UINT16
20
0
100
ERW
Setting of the maximum number of attempted automatic resets.
Содержание AFE200 4 Series
Страница 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Страница 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Страница 202: ...202 AFE200 Instruction Manual Appendix 3 Block Diagrams System Diagrams Index Drive overview Reference ...
Страница 203: ... AFE200 Instruction Manual 203 Commands ...
Страница 204: ...204 AFE200 Instruction Manual Digital inputs ...
Страница 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Страница 206: ...206 AFE200 Instruction Manual Analog inputs ...
Страница 207: ... AFE200 Instruction Manual 207 ...
Страница 208: ...208 AFE200 Instruction Manual Analog outputs ...
Страница 209: ... AFE200 Instruction Manual 209 Current Control ...
Страница 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Страница 211: ... AFE200 Instruction Manual 211 Functions ...
Страница 212: ......
Страница 213: ......