AFE200 • Instruction Manual
14.8 - COMMUNICATION/FAST LINK
The optional EXP-FL-XCAN-ADV card (generally inserted in slot 1) allows the number of I/Os man
-
aged by the drive to be increased, using an external device. Communication with the external device is
performed via CAN using the “DS401 Device profile for generic IO modules”.
For more details see manual 1S5F32_EXP-FL-XCAN-ADV.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.8.1
5702 FL address
UINT16
0
0
16
ERWZ
This parameter is used to enable the FastLink function and select whether the drive is
to be the master or slave. If used as a slave device, the address can be selected.
0
= Disabled
1
= Master
2
= Slave 1
X
= Slave X-1
16
= Slave 16
For the Pwm synchronisation to function properly, the address of the slave drive must
be configured in the same order as the physical connection.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.8.2
5818 FL bidirectional
ENUM
Enable
0
1
ERWZ
Enables/disables bi-directional Fast Link mode.
0
Disable
1
Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.8.3
5820 FL N of slave
UINT16
0
0
32767 ERWZ
It is a parameter related only to the master drive and it indicates which slave drives
need to be interrogated.
The encoding data used is an integer having set to 1 the bit corresponding to the
slaves that need to be interrogated:
- bit 0 (least significant bit)) is related to slave with address 2
- bit 1 is related to the slave with address 3
- …
- …until to the slave with address 16.
For example, if need to be interrogated slaves with address 2 and address 5, the
value will be 9 (1001 binary). If one or more slaves are not connected to the drops giv
-
ing no answer, it will produce a fast link alarm on the master drive. Fast link alarm on
the master will produce communication error to all the slaves connected.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
14.8.4
5710 FL sync slave type
ENUM
Off
0
2
ERWZ
This parameter is ineffective on the master drive.
On the slave drive this parameter is used to enable the function for generating Pwm
signals that are synchronised with the Pwm signals of the master. It is also possible to
enable the function for executing control tasks synchronised with execution of control
tasks of the master.
0
Off
Fastlink transfers information between the drives.
Содержание AFE200 4 Series
Страница 94: ...94 AFE200 Instruction Manual 7 DIGITAL INPUTS ...
Страница 97: ... AFE200 Instruction Manual 97 8 DIGITAL OUTPUTS ...
Страница 202: ...202 AFE200 Instruction Manual Appendix 3 Block Diagrams System Diagrams Index Drive overview Reference ...
Страница 203: ... AFE200 Instruction Manual 203 Commands ...
Страница 204: ...204 AFE200 Instruction Manual Digital inputs ...
Страница 205: ... AFE200 Instruction Manual 205 Digital outputs ...
Страница 206: ...206 AFE200 Instruction Manual Analog inputs ...
Страница 207: ... AFE200 Instruction Manual 207 ...
Страница 208: ...208 AFE200 Instruction Manual Analog outputs ...
Страница 209: ... AFE200 Instruction Manual 209 Current Control ...
Страница 210: ...210 AFE200 Instruction Manual Active Curr Config ...
Страница 211: ... AFE200 Instruction Manual 211 Functions ...
Страница 212: ......
Страница 213: ......