140
ADV200 • Quick start up guide - Specification and installation
Sizes
I
N
Rated output current
(f
SW
= default)
f
SW
Switching frequency
Derating factor
@U
LN
=400Vac
@U
LN
=460Vac
Default
Higher
K
V
K
T
K
F
(@ 8 kHz)
K
ALT
Heavy
duty
(A)
Light
duty
(A)
Heavy
duty
(A)
Light
duty
(A)
(1)
(2)
(3)
(4)
1007
2.5
4.3
2.3
3.9
8
10, 12
0.9
0.9
-
1.2
1015
4.3
5.8
3.9
5.2
8
10, 12
0.9
0.9
-
1.2
1022
5.8
7.6
5.2
6.8
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
1030
7.6
9.5
6.8
8.6
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
1040
9.5
13
8.6
11.7
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
2055
13
16.5
11.7
14.9
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
2075
16.5
23
14.9
20.7
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
2110
23
31
20.7
27.9
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
3150
31
38
27.9
34.2
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
3185
38
46
34.2
41.4
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
3220
46
62
41.4
55.8
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
4300
62
75
55.8
67.5
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
4370
75
87
67.5
78.3
4
6, 8, 10, 12
0.9
0.9
0.7
1.2
4450
87
105
78
94.5
4
6, 8
0.9
0.9
0.7
1.2
5550
105
150
94.5
135
4
6, 8
0.9
0.9
0.7
1.2
5750
150
180
135
162
4
6, 8
0.9
0.9
0.7
1.2
5900
180
210
162
189
4
6, 8
0.9
0.9
0.7
1.2
61100
210
250
189
225
4
6, 8
0.9
0.9
0.7
1.2
61320
250
300
225
270
4
6, 8
0.9
0.9
0.7
1.2
71600
300
385
270
347
4
-
0.9
0.9
-
1.2
72000
385
460
347
414
4
-
0.9
0.9
-
1.2
72500
460
590
414
531
2
-
0.9
0.9
-
1.2
73150
590
650
531
585
2
-
0.9
0.9
-
1.2
73550
650
730
585
657
2
-
0.9
0.9
-
1.2
400 kW
730
870
657
783
2
-
0.9
0.9
-
1.2
500 kW
870
1120
783
1008
2
-
0.9
0.9
-
1.2
630 kW
1120
1230
1008
1107
2
-
0.9
0.9
-
1.2
710 kW
1230
1380
1107
1242
2
-
0.9
0.9
-
1.2
900 kW
1600
1800
1440
1620
2
-
0.9
0.9
-
1.2
1000 kW
1900
2050
1620
1845
2
-
0.9
0.9
-
1.2
(1) K
V
: Derating factor for mains voltage at 460V
AC
(2) K
T
: Derating factor for 50°C ambient temperature (1 % each °C above 40°C)
(3) K
F
: Derating factor for higher switching frequency
(4) K
ALT
: Derating factor for installation at altitudes above 1000 meters a.s.l.. Value to be applied at each 100
m increase above 1000 m
I.e.: Altitude 2000 m, K
ALT
= 1,2 *10 = 12% di derating; I
N
derated = (100 - 12) % = 88 % I
N